Siemens Siemeca AMR AEW36.2 Скачать руководство пользователя страница 6

 

6/8 

Siemens Building Technologies 

Pulse Adapter AEW36.2 

CE1N2873en  

HVAC Products 

 

09.10.2003  

Then, keep the button depressed for more than 2 seconds. The installation telegrams 
will be sent: 
 

 

 
The display shows the number of the remaining installation telegrams for each channel. 

Technical data 

 conformity  

89/336/EEC (EMC directive) 
1999/5/EEC (R&TTE directive) 

Degree of protection   

IP 54 to EN 60 529 

Safety class  

III to EN  60 950  

Electromagnetic compatibility 
Immunity 

 
Emissions 
 
Security of IT equipment  

 
EN 301 489 –1 / -3 V1.2.1 (2000-08) 

EN 61000-6-2 :1999 
EN 300 220 –1 V1.3.1 (2000-09) 
 

- 3 V1.1.1. (2000-09 

EN 60 950  

Operating voltage 

DC 3 V 

Life expectancy   

12 +1 years 

Nominal frequency  

868.3 MHz  

Transmitting power   

< 5 mW   

Transmission frequency 

6 times / 24 hours 

Perm. ambient temperature  
 

Transport and storage  

 

Operation 

 

25...+60 °C 

0...55 °C 

Weight 

0.3 kg  

 

Содержание Siemeca AMR AEW36.2

Страница 1: ...e adapter is a component of the Siemeca AMR system It is for installations where consumption meters with pulse output are used the data of which shall be collected by the Siemeca AMR system Such devices can be meters for hot water cold water gas electricity etc Functions Acquisition of the pulses delivered by the connected consumption meters Monitoring the connecting cable in the case of metering ...

Страница 2: ... 01 46 83 61 E Mail georg bendlin siemens com With the correct data set installed the following types of meters can be connected Water meters with pulse output Heat meters with pulse output Gas meters with pulse output Steam meters with pulse output Electricity meters with S0 interface note an additional WHZ S0 converter is re quired refer to Data Sheet CE1N2867 Technical design The pulse adapter ...

Страница 3: ... dis play a long press produces a change from one display level to the next The first 2 display levels show current meter related values The other 2 dis play levels show 13 end of the month values of the relevant meter Display levels 1 and 2 meters 1 and 2 are identical Zähler 1 Zähler 2 Zähler 1 Zähler 2 Statistik Statistik Display level meter 1 or meter 2 In the event of fault severe constant fa...

Страница 4: ... consumption values and the date of that consumption over the past 13 months Zähler 1 Zähler 2 Zähler 1 Zähler 2 Statistik Statistik Display level meter 1 statistics or meter 2 statistics m Alternate display of consumption value and last day of the previous month notation dd mm yy m Alternate display of consumption value and last day of the previous month notation dd mm yy Displays continue for th...

Страница 5: ...ck Then close the housing Commissioning notes The pulse adapter is to be programmed during installation Enter the following data for each channel Type of pulse source Reed switch Reed switch with NAMUR Open Collector etc per input Type of medium gas water etc per input Physical variable kWh m3 etc per input Pulse valency per input Set day per input 1 set day per year Meter readings when commission...

Страница 6: ... directive 1999 5 EEC R TTE directive Degree of protection IP 54 to EN 60 529 Safety class III to EN 60 950 Electromagnetic compatibility Immunity Emissions Security of IT equipment EN 301 489 1 3 V1 2 1 2000 08 EN 61000 6 2 1999 EN 300 220 1 V1 3 1 2000 09 3 V1 1 1 2000 09 EN 60 950 Operating voltage DC 3 V Life expectancy 12 1 years Nominal frequency 868 3 MHz Transmitting power 5 mW Transmissio...

Страница 7: ...ith pulse output U1 AEW36 2 pulse adapter P1 P2 Meter with pulse output INP 1 INP2 U1 P1 P2 N1 N2 INP INP OUT OUT AC 230 V S0 S0 blue white white red Connection of electricity meters with S0 inter face U1 AEW36 2 pulse adapter P1 P2 Electricity meters with pulse output N1 N2 WHZ SO pulse converter Dimensions 90 79 95 5 79 27 3 3 5 39 5 Dimensions in mm Connecting cable length is 350 mm ...

Страница 8: ... meters WFC26 WFH26 Data Sheets CE1N5341 CE1N5343 Network node WTT16 Data Sheet CE1N2874 Software ACS ACT Data Sheet CE1N2875 PC radio module WTZ RM Data Sheet CE1N2876 M bus central unit OZW10 Data Sheet CE1N5362 The information provided in this Data Sheet only gives general descriptions and general technical features which in the case of specific applications may not necessarily apply or which m...