Siemens Building Technologies
Pulse Adapter AEW36.2
CE1N2873en
HVAC Products
09.10.2003
Data set number (describes the type of meter).
h
Number of operating hours.
Primary address
When pressing the button for more than 2 seconds in this
step, the transmission of 8 installation telegrams will be
started.
IrDA primary address.
Software version.
Installation telegrams:
Sending installation telegrams; the 2 digits indicate the
remaining telegrams for the 2 channels of the pulse
adapter.
Display levels 3 and 4 (meter 1 statistics and meter 2 statistics) are identical. They
show the consumption values and the date of that consumption over the past 13
months.
Zähler 1 Zähler 2 Zähler 1 Zähler 2
Statistik Statistik
Display level meter 1 statistics or meter 2 statistics
m³
Alternate display of consumption value and last day of the
previous month (notation: dd.mm.yy).
m³
Alternate display of consumption value and last day of the
previous month (notation: dd.mm.yy).
...
Displays continue for the last 13 months.
Error code
Description of fault
2
Number of operating hours
6
Pulse acquisition channel 1 open-circuit
7
Pulse acquisition channel 1 short-circuit
8
Pulse acquisition channel 2 open-circuit
9
Pulse acquisition channel 2 short-circuit
B
Number of communication via IrDA exceeded
C
Number of communication via M-bus exceeded
F
Device not initialized
Error code