User Manual SICLOCK GPS1000
10
Version 1.0
Order number 2XV9450-1AR82-BA
Parameterization required for SICLOCK TM:
1. Set input E1 to DCF passive.
2. Set time zone according to the location in relation to GMT (see SICLOCK TM manual)
Fig. 3 shows in schematic diagram the connection of GPS1000 to SICLOCK TM or to a PC with the lightning pro-
tection module 2XV9450-1AR83. The parts illustrated in photos and the grey cables are included in the scope of
delivery for the complete package SICLOCK GPS1000 except of the lightning protection module.
The red and green cables must be made available on site.
The lightning protection module should be installed in the building as near as possible to where the antenna
cable enters the building. Please pay attention to “
IN” and “OUT” !
Important:
It is absolutely essential that the earth cable shown in green and connected to the DIN rail (cross section 25 sq.
mm or more) is connected in the shortest possible way and as straight as possible to a foundation earth.
Fig 3: Installation diagram for SICLOCK TM and PC with lightning protection module.
Power supply
24-230 V/DC or 48-230 V/AC