Engineering via SICAM WEB
176
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.9.2.2 Parameters with Assignment on the Master Control Module
This data can be changed – for each category – in the table for the signal generation:
Category
Parameter
Meaning
Communication control
message
Control_function_(COM)
•
Revision function
•
Test function
•
Block function
PRE
Protocol element
Station_(COM)
Station number (selective 0…99 or all)
CASDU1_(COM)
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
CASDU2_(COM)
Address of the datapoint. The complete ad-
dress consists of CASDU1, CASDU2, IOA1,
IOA2 and IOA3. CASDU1 and CASDU2 =
255 means no spontaneous transmission.
Function_group_(COM)
Function group number (0…255)
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
Decentral archiving
Function_(DEAR)
•
Archive data
•
Address main directory
•
Address subdirectory
•
Address file
QID-BSE
Source identification basic system element
QID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
QID-SSE
Source identification supplementary system
element
Error message detailed
diagnostics table
SSE
Supplementary system element
Diagnostic_class
In case of "all bits, all records, all classes" the
parameter "diagnostic record" and "diagnostic
bit" are not significant
Diagnostic_record
Diagnostic record 0…254 = record number
whitin the selected diagnostic class
255 = sum of all bits of all records (the pa-
rameter "diagnostic bit" is not significant)
Diagnostic_bit
Bit number (0…15; all bits)
Error message sum diag-
nostics table
Error_location/BSE
Error location/basic system element
Error_location/SSE
Error location /supplementary system ele-
ment
Error type
Error class in the diagnosis
Parameter of measured
values ACP1703
Kind_of_parameter
•
According NUC
•
Threshold value
•
Smoothing factor
•
Lower limit for transmission of measured
values
•
Upper limit for transmission of measured
values
•
Activation parameters for measured values
Interrogation-group
General interrogation (group 1…16; none)
Содержание SICAM CMIC
Страница 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 10: ...Open Source Software Used in SICAM CMIC 10 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 20: ...Table of Contents 20 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 Glossary 405 ...
Страница 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 130: ...Engineering via SICAM TOOLBOX II 130 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 386: ...Set Up Dial Up Connection via PPP 386 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 394: ...Install Security Certificate 394 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Страница 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...