Redundancy via SCA-RS
SICAM RTUs, SICAM AK Redundancy
Unrestricted
41
DC2-026-2.07, Edition 10.2016
1.3
Redundant Automation Units
Connection between both BSEs over HSL:
The High Speed Link (HSL) is used for the synchronization of both redundant BSEs
(C-CPUs).
In the case of AU redundancy the HSL is established with a fiber optic cable.
Exception
: If the distance between both AUs is more than 200 m, in all cases the redundancy
synchronization must take place over a separate fast data connection.
That causes a high load in the AU. Therefore take the following into consideration:
•
Parameterize a connection between both AUs on that PRE, that is to be responsible for
the synchronization of both BSEs
•
The PRE for this data connection must be coupled to that BSE which is to be
synchronized.
•
Use cycle times that are long enough for your CAEx
plus
application
•
Make sure, that both BSEs have an identical configuration and that they are loaded with
the same FW revision and the same parameters (state).
Содержание SICAM AK
Страница 6: ...Preface 6 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 8: ...Open Source Software 8 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 12: ...Table of Contents 12 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 126: ...Configuration of SICAM AK and CP 6010 126 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 127: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 127 DC2 026 2 07 Edition 10 2016 ...
Страница 128: ...Configuration of SICAM AK and CP 6010 128 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 129: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 129 DC2 026 2 07 Edition 10 2016 ...
Страница 167: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 167 DC2 026 2 07 Edition 10 2016 ...