Redundancy via CP-6010
SICAM RTUs, SICAM AK Redundancy
Unrestricted
107
DC2-026-2.07, Edition 10.2016
2.5
SICAM AK Switchover Settings
This section describes exemplarily the engineering of the redundancy switchover in the
SICAM TOOLBOX II for the system SICAM AK.
2.5.1
Communication Settings
The following settings must be performed in order to set up the functionality of the redundancy
in both modes of operation (“global switchover”, “line-by-line switchover”).
2.5.1.1 System-Technical Settings
In both systems SICAM AK, select under the M-CPU the menu
connection definition
and
enter the IP address of the respective CP-6010.
Select the menu
IP address
and enter the IP addresses of the corresponding system
SICAM AK.
Select the menu
104 parameters
and enter the IEC 60870-5-104 timeout values.
Содержание SICAM AK
Страница 6: ...Preface 6 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 8: ...Open Source Software 8 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 12: ...Table of Contents 12 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 126: ...Configuration of SICAM AK and CP 6010 126 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 127: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 127 DC2 026 2 07 Edition 10 2016 ...
Страница 128: ...Configuration of SICAM AK and CP 6010 128 Unrestricted SICAM RTUs SICAM AK Redundancy Edition 10 2016 DC2 026 2 07 ...
Страница 129: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 129 DC2 026 2 07 Edition 10 2016 ...
Страница 167: ...Configuration of SICAM AK and CP 6010 SICAM RTUs SICAM AK Redundancy Unrestricted 167 DC2 026 2 07 Edition 10 2016 ...