Parameter Settings
70
Neutral Overcurrent
Relay Settings
% Max Rating
115%
125%
150%
200%
250%
Max Rating
(A)
Pickup (A)
400
460
500
600
800
1000
800
920
1000
1200
1600
2000
1200
1380
1500
1800
2400
3000
1600
1840
2000
2400
3200
4000
2000
2300
2500
3000
4000
5000
2500
2875
3125
3750
5000
6250
3200
3680
4000
4800
6400
8000
4000
4600
5000
6000
8000
10000
5000
5750
6250
7500
10000
12500
Overcurrent Demand
Alarm Settings
% I
n
60%
70%
80%
90%
95%
100%
I
n
= Rating Plug
(A)
Pickup (A)
200
120
140
160
180
190
200
225
135
157
180
202
213
225
250
150
175
200
225
237
250
300
180
210
240
270
285
300
350
210
245
280
315
332
350
400
240
280
320
360
380
400
450
270
315
360
405
427
450
500
300
350
400
450
475
500
600
360
420
480
540
570
600
700
420
490
560
630
665
700
800
480
560
640
720
760
800
1000
600
700
800
900
950
1000
1200
720
840
960
1080
1140
1200
1600
960
1120
1280
1440
1520
1600
2000
1200
1400
1600
1800
1900
2000
2500
1500
1750
2000
2250
2375
2500
3000
1800
2100
2400
2700
2850
3000
3200
1920
2240
2560
2880
3040
3200
4000
2400
2800
3200
3600
3800
4000
5000
3000
3500
4000
4500
4750
5000