Parameter Settings
66
.
Long Time Protection
Settings
% I
n
50%
60%
65%
70%
75%
80%
85%
90%
95%
100%
I
n
= Rating Plug (A)
Pickup (A)
200
100
120
130
140
150
160
170
180
190
200
225
112
135
146
157
168
180
191
202
213
225
250
125
150
162
175
187
200
212
225
237
250
300
150
180
195
210
225
240
255
270
285
300
350
175
210
227
245
262
280
297
315
332
350
400
200
240
260
280
300
320
340
360
380
400
450
225
270
292
315
337
360
382
405
427
450
500
250
300
325
350
375
400
425
450
475
500
600
300
360
390
420
450
480
510
540
570
600
700
350
420
455
490
525
560
595
630
665
700
800
400
480
520
560
600
640
680
720
760
800
1000
500
600
650
700
750
800
850
900
950
1000
1200
600
720
780
840
900
960
1020
1080
1140
1200
1600
800
960
1040
1120
1200
1280
1360
1440
1520
1600
2000
1000
1200
1300
1400
1500
1600
1700
1800
1900
2000
2500
1250
1500
1625
1750
1875
2000
2125
2250
2375
2500
3000
1500
1800
1950
2100
2250
2400
2550
2700
2850
3000
3200
1600
1920
2080
2240
2400
2560
2720
2880
3040
3200
4000
2000
2400
2600
2800
3000
3200
3400
3600
3800
4000
5000
2500
3000
3250
3500
3750
4000
4250
4500
4750
5000
Long Time Protection
Delay Settings (at 6x)
Time (s)
2.5
4
5.5
8
10
14
17
21
25
30