![Siemens SENTRON 3KF LV HRC Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/siemens/sentron-3kf-lv-hrc/sentron-3kf-lv-hrc_manual_380322091.webp)
Further accessories
8.4 8UD door-coupling rotary operating mechanism
3KF switch disconnectors with fuses
Manual, 09/2019, L1V30580914002A-01
89
8.4.3.2
Calculating the length of the shaft/cutting the shaft
3KF with front operating mechanism
mm
A min
A max
B
C
3KF2
293.0
386.5
93.5
43
3KF3
355.5
422.0
129.8
43
3KF4
320.0
391.0
110.0
43
3KF5
307.0
405.5
152.5
43
Length of the shaft
Size of the
3KF
Coupling drivers
With tolerance compensation
Without tolerance compensation
A [mm]
Tolerance
B [mm]
A [mm]
Tolerance
B [mm]
1, 2
X - 96
+ 5
X - 111
X - 54
+5
X - 69
3
X - 99.5
+10
X - 136.5
X - 57.5
+10
X - 94.5
4
X - 103
+10
X - 153
X - 61
+10
X - 111
5
X - 117.5
+10
X - 195.5
X - 75.5
+10
X - 153.5
X = Min. clearance from mounting plate to front of door
Size of the 3KF
Min. clearance X [mm]
1, 2
138.5
3
169
4
185.5
5
228
Содержание SENTRON 3KF LV HRC
Страница 1: ...3KF switch disconnectors with fuses ...
Страница 2: ......
Страница 8: ...Table of contents 3KF switch disconnectors with fuses 6 Manual 09 2019 L1V30580914002A 01 ...
Страница 110: ...Maintenance 3KF switch disconnectors with fuses 108 Manual 09 2019 L1V30580914002A 01 ...
Страница 148: ...Conversion tables 3KF switch disconnectors with fuses 146 Manual 09 2019 L1V30580914002A 01 ...
Страница 157: ......
Страница 158: ......