Connection and wiring
7.1 Main circuit connection
3KF switch disconnectors with fuses
Manual, 09/2019, L1V30580914002A-01
51
7.1.3
Flat terminals
Sizes 2 to 4
Size 5
DIN ISO 46234 [mm
2
]
DIN ISO 46235 [mm
2
]
[mm x mm]
3KF2...-..F..
1 × 2.5 ... 95
2 x 2.5 ... 50
1 × 25 ... 70
2 x 25 ... 50
1 × 15 x 3
1 x 20 x 3
3KF3...-..F..
1 × 6 ... 120
2 × 6 ... 120
1 × 16 ... 120
2 × 16 ... 120
1 × 20 × 3
1 × 25 × 3
3KF4...-..F..
1 × 6 ... 240
2 × 6 ... 150
1 × 16 ... 185
2 × 16 ... 150
1 × 30 × 4
1 × 30 × 10
3KF5...-..F..
1 × 25 ... 240
2 × 25 ... 240
1 × 25 ... 300
1 × 30 × 10
1 × 50 × 10
2 × 50 × 5
WARNING
Fire hazard
Incorrect connection of cables may cause flashovers between the terminals.
•
The terminal screw must be correctly aligned – with the nuts on top.