Connection
6.2 Connecting to the circuit
3KC0 manual transfer switching equipment
44
Manual, 09/2018, L1V30368969105-01
6.2.5
Connecting the terminals for sizes 3, 4 and 5
Flat terminal
Since the 3KC0 transfer switching equipment has flat terminals, you can connect it to the
power supply system using cable lugs or busbars.
Dimensions for busbar holes
Size of transfer
switching equip-
ment
A (mm)
B (mm)
C (mm)
D (mm)
3
< 15.5
–
–
11
4
< 21
–
–
14
5
< 19
23 … 29
13
14
6.2.6
Connecting transfer switching equipment sizes 3, 4 and 5
To connect the 3KC0 transfer switching equipment properly, you must first mount the
bridging bar accessory. The steps listed below describe the mounting of the bridging bar and
the connection to the power supply system.
6.2.6.1
Connecting a bridging bar to sizes 3, 4 and 5
WARNING
Hazardous voltage!
Ensure there is no live voltage before mounting the bridging bars.
Note
In addition to the terminal covers, you must also connect side panel covers for lateral touch
protection of the connection side at which the bridging bars are used (usually the load side).