Appendix
A.3 Storage conditions
3KC0 manual transfer switching equipment
132
Manual, 09/2018, L1V30368969105-01
A.2.3
Altitude conditions
●
Up to 2000 m: No derating
●
For higher altitudes, the following derating correction factor must be factored in:
Correction factor K
a
2000 m < A
1)
≤
3000 m
3000 m < A
1)
≤
4000 m
U
e
0.95
0.8
I
e
0.85
0.85
1)
Height
A.3
Storage conditions
A.3.1
Temperature
Store the transfer switching equipment between −50
°C and +80 °C.
A.3.2
Storage conditions
●
Maximum storage time: 12 months
●
Storage in a dry, non-corrosive, salt-free environment is recommended.
A.3.3
Storage position
If the 3KC0 transfer switching equipment is stored on a pallet, the number of stackable
layers is not unlimited. You can find more information in the table below:
Size
Stackable layers
1 and 2
10
3
5
4
3
5
2