Connecting up
4.3 Wiring rules
SCALANCE XR-100WG
24
Operating Instructions, 05/2017, C79000-G8976-C455-01
Autonegotiation
Autonegotiation means the automatic detection/negotiation of the transmission rate and the
operating mode of ports at the opposite end. This makes it possible to configure different
devices automatically.
Two components connected to a link segment can exchange information about the transfer
and can adapt their settings to each other. The mode with the highest possible speed is set.
Note
•
If a port operating in the "Auto negotiation" mode is connected to a partner port that is not
operating in the"Auto negotiation" mode, the partner port setting must be fixed.
•
Devices not supporting "Auto negotiation" must be set permanently to 100 Mbps or
10 Mbps half duplex.
4.3
Wiring rules
When wiring, use cables with the following AWG* categories or cross sections.
Wiring rules for ...
Spring-loaded terminals
connectable cable cross
sections for flexible cables ...
without wire end ferrule
0.75 - 2.5 mm
2
AWG: 20 - 14
with wire end ferrule**
0.75 - 2.5 mm
2
AWG: 20 - 14
with TWIN wire end ferrule**
0.75 - 1 mm
2
AWG: 20 - 18
Stripped length of the cable
8 - 10 mm
Wire end ferrule according to DIN 46228 with plastic ferrule**
8 - 10 mm
* AWG: American Wire Gauge
** See note "Wire end ferrules"
Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped
crimp cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
Содержание SCALANCE XR-100WG Series
Страница 8: ...Table of contents SCALANCE XR 100WG 8 Operating Instructions 05 2017 C79000 G8976 C455 01 ...
Страница 10: ...Safety notices SCALANCE XR 100WG 10 Operating Instructions 05 2017 C79000 G8976 C455 01 ...
Страница 30: ...Upkeep and maintenance SCALANCE XR 100WG 30 Operating Instructions 05 2017 C79000 G8976 C455 01 ...
Страница 36: ...Dimension drawings SCALANCE XR 100WG 36 Operating Instructions 05 2017 C79000 G8976 C455 01 ...