background image

 

 

Specification for SiteI/O 32/0

 

 

 

 

 
DESCRIPTION:  

The SiteI/O 32/0 is part of the SiteI/O-Line, which allows a complete SiteScan 

monitoring/control system to be built a piece at a time.  It is a 32 bit microprocessor-based device 
designed to monitor up to thirty-two analog, digital, and/or dry contact type signals.  Individual hardware 
jumpers set signal-type selections.  Screw terminal blocks are provided to terminate power, 
communication, and input signal wiring.  
 

DIMENSIONS: 

Module: 

11 5/16” H x 11 5/16” W x 2 3/4” D 

 

 

28.73 cm H x 28.73 cm W x 7 cm D 

 
 

Enclosure:  

20" H x 18" W x 2.87" D 

 

(Painted Steel) 

508mm x 457.2mm x 72.89mm 

 
 

See Enclosure Diagrams for mounting options. 

 

POWER:

 24VAC 

±

 10%, 50-60 Hz., 35 VA power consumption 

 

(120/24VAC 40VA Transformer available) 

 

INPUTS: 

Thirty-two universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor.

 

 
ENVIRONMENTAL  
OPERATING RANGE:

  0

°

 to 130

°

 F (-17.8

°

 to 54.4

°

 C), 10 to 90% relative humidity, non-condensing 

 

COMMUNICATION:

 

(1) CMnet EIA-485 Port - Control Module network screw terminals 

 

Switch selectable baud rates ARC156 / 9600 or 38.4bps 

Recommended wire is: MAGNUM Cable pn A3-ARC-156-2 

 
 

(32)  Analog and/or Digital - screw terminals 

 

 

Jumper Selectable inputs 

 

 

Thermistor - 10k ohm @ 77

°

 F, 25

°

 

 

0 to 5 VDC - 10k ohm max source impedance 

 

 

4 to 20mA -  24VDC loop power, 250 ohm input 

 

 

Dry Contact - 0.5mA sense current 

 
MEMORY: 

1 MB Flash Memory, 1 MB Non-volatile battery backed RAM.

 

 
PROTECTION:

 

Voltage, current, and ESD protection on incoming power. 

 

  

Liebert Corporation

                          Page 

1 of 5                                                  SL-28073 

Rev. 4; 7/03 

Содержание SiteI/O 32/0

Страница 1: ...nting options POWER 24VAC 10 50 60 Hz 35 VA power consumption 120 24VAC 40VA Transformer available INPUTS Thirty two universal inputs configurable for 0 5VDC 0 20mA or thermistor ENVIRONMENTAL OPERATING RANGE 0 to 130 F 17 8 to 54 4 C 10 to 90 relative humidity non condensing COMMUNICATION 1 CMnet EIA 485 Port Control Module network screw terminals Switch selectable baud rates ARC156 9600 or 38 4b...

Страница 2: ...LEDs CMnet Mode Jumper 2 3 4 7cm 0 20 mA dry contact Th ermistor 0 5Vdc Mode Select Universal Input 1 16 B Gnd Loop Power A Input Signal Expansion I O Expansion I O Auxiliary Port Device Con duc tors O n ly Use C op p er 35 V A 1 5 A 24 V ac 50 60 Hz C las s 2 Tx Rx Error Run Power A 8 B IN 4 7 13 A IN 7 14 B 16 B A IN 8 15 10 IN 5 B 9 A IN 6 12 B 11 A IN 2 4 B 3 A 5 A IN 3 6 B 2 IN 1 B 1 A Mode S...

Страница 3: ...PW R OUT GND PW R OUT GND OU T OUT OU T Un iv ers a l In p ut M o d e S el ec t V PA SS IVE TRA NSDU CER TO M OD ULE GND THER M ISTOR 4 2 0 m A 1 2 V o r 2 4V L OOP I NPUT A B A B A B A B A B A B A B A B A B A B A B A B A B A B In p ut s 5 V M ax 20 m A M a x A B A B A B A B A B A B A B A B A B A B A B A B A B A B Liebert Corporation Page 3 of 5 SL 28073 Rev 4 7 03 ...

Страница 4: ...MMUNICATIONS WIRING DIAGRAM Net Ne t Shield Net Net CMnet 18 24 ga Twisted Pair Shielded Low Impedance Low Capacitance Recommended wire is Magnum Cable A3 ARC 156 2 ENLOSURE DIAGRAMS Liebert Corporation Page 4 of 5 SL 28073 Rev 4 7 03 ...

Страница 5: ...Specification for SiteI O 32 0 Enclosure Wall Mounting Enclosure Floor Mounting with Brackets Liebert Corporation Page 5 of 5 SL 28073 Rev 4 7 03 ...

Отзывы: