3.2.1 Power supply unit circuit board SMP 20 (Fig. 2)

- Transformer terminal 

20V, 50Hz.

- Relay 

which can be programmed from the central  

  control unit.
- Four +12 V voltage outputs 

(+1, +3, +4, +6) each of  

  which is protected by a fuse (F2 to F5).  

 

- Output 

for mains supply indication (not fused).

- E-Bus connection to central control unit 

(B1-, B2, B3,  

  B4+). B4+ is protected by fuse F1.
- Pre-wired battery terminal 

is protected by fuse F6.

- Address key 

P

.

- LED 

fl ashes if the E-Bus communication is correct.

- LED 

for mains supply indication.

-  The adjustment of potentiometer 

,

must not be disturbed.

3.3 Fit housing (Fig. 3)

1 -  Mark the drilling position for the four mounting holes 

Q

.

2 - Drill the holes and insert plugs.
3 -  Screw in the screws leaving approximately 1.5 cm 
      proud (Fig. 3B).
4 -  From the back, snap the spacers into the slots provided 
      at the four mounting holes (Fig. 3A).
5 -  Pass the connecting cable through the opening 

W

 provi 

      ded and hang the housing base on the screws
6 -  Tighten the mounting screws.

3.4 Fit circuit boards SMT 11 or SMR 11 "optional" 
(Fig.4)

1 - Engage the mounting studs (provided with the circuit
      boards) in the holes provided (Fig. 4A).
2 - Fit circuit boards (Fig. 4B).

 

                         Fuses

No.        Terminal         Function          Type

F1         B4+                E-Bus              F2AL
F2         +1                  +12V               F2AL
F3         +3                  +12V               F2AL
F4         +4                  +12V               F2AL
F5         +6                  +12V               F2AL
F6         + Batt.            Battery             T2AL

Q

Q

W

1,5 cm

B

Ø 6 mm

S6

4,5 x 45

Содержание SAP 20

Страница 1: ...e with Installation instructions One wiring diagram 3 Mounting instructions The SAP 20 external power supply unit is designed for moun ting in dry indoor rooms It must not be exposed to dripping or splashing water 3 1 Open cover Fig 1 1 Slacken cover screw W 2 Remove cover 3 2 Product overview Fig 1 Housing E Power supply assembly circuit board SMP 20 I Transformer SMU 31 U Mains supply terminals ...

Страница 2: ...ter U O must not be disturbed 3 3 Fit housing Fig 3 1 Mark the drilling position for the four mounting holes Q 2 Drill the holes and insert plugs 3 Screw in the screws leaving approximately 1 5 cm proud Fig 3B 4 From the back snap the spacers into the slots provided at the four mounting holes Fig 3A 5 Pass the connecting cable through the opening W provi ded and hang the housing base on the screws...

Страница 3: ... the options SMT 11 SMR 11 must be connected to the central control unit via the E Bus B1 B2 B3 B4 It may be routed in parallel to other accessories If shielded cable is used the shield may not be laid on the housing of the SAP 20 The shields of all cables must be connected at one point e g at one of the NC terminals of SMT 11 or SAR 11 4 3 Tamper contact Fig 7 The tamper contact of the housing mu...

Страница 4: ...he screws the cover can be lifted gently swung downwards and suspended in the base 7 Technical data Mains voltage 240V 50Hz Power consumption 230V 230mA Mains supply fuse 500 mA slow blowing Output power 12VDC 2 3 A Max ripple at 2 3 A 60mVpp Relay single pole changeover 48V 5A Battery min V 2 optional 12V 24Ah Operating temperature 10 C to 40 C Steel housing 1 5 mm Dimensions in mm H 500 x W 365 ...

Отзывы: