Data logger
The data logger (optional) permits archiving of data that the user can select from a
predefined set of values. The data logger contains 4 archives whose 8 channels
can be assigned. The data can be assigned to any of the channels. Parameteriza-
tion is performed with the service software.
Archive
Time base
Storage depth
Averaging time for
maximum
Hourly archive
1 hour
45 days
1 hour
Daily archive
1 day
65 days
1 hour
Monthly archive
1 month
15 months
1 hour
Yearly archive
1 year
15 years
1 hour/24 hours
*) For measuring periods below 1 hour, the largest value from the maximum values
calculated within 1 hour applies
The data are recorded with their values and time stamps. Parameterization and
readout are performed via the optical interface with the service software.
Data transmission is in a manufacturer-specific format.
Value set for data to be recorded
Meter readings at the
end of the period for...
Energy
Tariff register 1, 2, 3
Volume
Operating time *)
Fault duration *)
Pulse input 1
Pulse input 2
*) Depending on parameter setting: Hours or days
Instantaneous values at
the end of the period
for...
Power
Flow rate
Flow temperature
Return temperature
Temperature differential
Error display
Maximum for...
Power
Flow rate
Flow temperature
Return temperature
Temperature differential
Note