background image

4/10

Siemens

RWD62 Universal controller

CE2N3342en

Building Technologies

2017-12-05

The universal input X1 is used as the primary input for a LG- Ni 1000 temperature sen-
sor, a Pt 1000 temperature sensor or a DC 0…10 V active input.

The universal input X2 is used as the secondary input for a LG-Ni 1000 temperature
sensor, a Pt 1000 temperature sensor, an active/passive remote setpoint transmitter or
a DC 0…10 V active input.

The digital input D1 is used to select the day or night changeover. Changeover occurs
via potential-free contacts between D1 and M.

Each output Y (Y1, Y2) can be configured for either reverse or direct acting. The modu-
lating voltage output (Y…) controls the devices requiring a DC 0…10 V signal.

Ventilating plant with temperature control

X1

Room temperature

Y1

Heating, reverse action

Y2

Cooling, direct action

X1

Y2

Y1

Temp.

RWD62

Y

33

42

s0

1

One of the following auxiliary functions can be selected:

·

  PI limiter function (absolute and relative)

·

  Remote setpoint function

·

  Cascade control function

·

  Setpoint compensation

·

  Winter/summer operation

·

  Maximum priority

Additionally, the day and night operation mode is available.

The limiter function with PI control enables absolute
(or relative) maximum or minimum limitation of the
supply air temperature (X2).
When the value drops below or exceeds the limiter
setpoint, the limiter function controls and takes priority
over the main setpoint.

X1

Y2

Y1

Temp.

RWD62

Y

X2

33

42

s0

2

A remote setpoint transmitter (FZA21.11, QAA25 or
QAA25/AP), connected to X2 and configured accord-
ingly, enables setpoint adjustment.
Active measurement from 0…10 V DC corresponding
adjustable range from –100 to 8000
Passive measurement from 0…1000

W

 corresponding

adjustable range from –100 to 8000

X1

Y2

Y1

Temp.

RWD62

Y

X2

33

42

s0

3

Universal input X1

Universal input X2

Digital input D1

Analog outputs

Example

Auxiliary functions

PI limiter function

Remote setpoint

Cascade control

Содержание RWD62

Страница 1: ...Pt 1000 temperature sensors and DC 0 10 V signals Unit can be set as C F or no specified unit Two modulating outputs with DC 0 10 V signal outputs direct or reverse action One digital input for day night changeover Entering or changing of all data via operating buttons on the controller possi ble without additional tools PC connection for downloading canned applications via the software tool Use T...

Страница 2: ...ction Cascade control function Setpoint compensation Winter summer operation Maximum priority Digital input D1 for setpoint changeover day night Type summary Inputs Outputs Type Reference Universal Digital Analog Digital 2 1 2 0 RWD62 Name Type Protective small enclosure for wall mounting ARG62 21 Protective big enclosure for wall mounting ARG62 22 Software Tool S3341A031EN0 Equipment combinations...

Страница 3: ...on and setting parameters via the push buttons on the controller or the software tool The RWD62 controller can be programmed as follows One sequence Y1 or Y2 reverse or direct acting Two sequence Y1 and Y2 reverse and direct acting or Y1 and Y2 reverse and reverse acting or Y1 and Y2 direct and direct acting Y1 Output Voltage Setpoint Load 3342d01 3342d02 Y1 Output Voltage Load Y2 Setpoint Reverse...

Страница 4: ...3342s01 One of the following auxiliary functions can be selected PI limiter function absolute and relative Remote setpoint function Cascade control function Setpoint compensation Winter summer operation Maximum priority Additionally the day and night operation mode is available The limiter function with PI control enables absolute or relative maximum or minimum limitation of the supply air tempera...

Страница 5: ...perature setpoint as controlled by the outside temperature 3342s06 X2 Y1 Temp RWD62 Y X1 A digital switch or analogue input between termi nals X2 and M can be used to implement win ter summer changeover Digital changeover When the contact is closed summer operation is selected Reverse acting output Y1 only is set to direct action cooling Analog changeover When the X2 input exceeds the setpoint sum...

Страница 6: ...ated by the buttons on the controller front Additional tools are not necessary A 9 pin port is provided for optional programming via the software tool 3342z01 The LCD shows the following information for normal operation Current operating values maximum 4 digits Current setpoints day night Application number Output voltage value Control sequencing diagram Auxiliary input value Selected auxiliary fu...

Страница 7: ... AC 24 V operating voltage The low voltage must comply with the requirements for safety extra low voltage SELV as per EN 60730 Use safety insulating transformers with double insulation as per EN 60742 they must be designed for 100 on time When using several transformers in one system the connection terminals G0 must be galvanically connected Supplying voltages above AC 24 V to low voltage connecti...

Страница 8: ...duct environmental declaration CE1E3343en contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal Screw terminals for cables with min 0 5 mm dia max 2 x 1 5 mm2 or 2 5 mm2 RWD62 0 277 kg The documents can be downloaded from http siemens com bt download The device is considered electrical and electroni...

Страница 9: ...for control commands D M Current consumption DC 15 V 15 mA Range Maximum current DC 0 10 V 1 mA Internal diagram G0 RWD62 Y2 D1 M X1 M X2 M G M Y1 M Tool 3342g01 D1 Digital input G G0 AC 24 V supply SELV AC 24 V power supply M Ground G0 for signal inputs universal inputs and analog outputs X1 Signal input main input LS Ni 1000 Pt 1000 and 0 10 V DC X2 Signal input aux input LS Ni 1000 Pt 1000 0 10...

Страница 10: ...P computer the TOOL signal ground is gal vanically connected to G0 inside the controller If the signal line of the computer is grounded to Earth the G0 line after TOOL connection will be Earthed as well This will change from SELV to a PELV Dimensions ARG62 21 150 200 61 5 48 5 ARG62 22 345 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 2...