background image

RWD45U Controller Installation and Commissioning Guide 

Document Number 129-409 

 

October 5, 2009 

Siemens Industry, Inc. 

Page 7 of 13

 

 

 

Initial Program 
Settings 
(New Controller) 

There are five levels of parameter setting (PS) modes: PS1 through PS4, and a 
setpoint mode. Each PS has a set of default parameters, which can be changed during 
commissioning. 

When powered the first time, the controller will proceed to PS1 with default 
application 10. See below for commissioning steps. 

PS 1 – Application Settings 

Range/Type 

Default  

Enter application number 

10 through 99 

10 

Select number of compressor stages 

1-, 2- or 3-stage 

2-stage 

Select reversing valve output – On or Off during no demand 

On or Off  

Off 

After completing PS1, the user has the option to progress to setpoint mode (only for new RWD) by waiting for 
two seconds and default parameters will be accepted. If parameters PS2 through PS4 need to be adjusted, 
press the 

+

 

σ

 button immediately to the next PS (see 

Commissioning Flowchart

). 

 

PS 2 – Input X1, X2 and X3 

Range/Type 

Default  

Select unit 

°F or °C 

°F 

Select main sensor X1 

Ni1000, Pt1000, 0 to 10V 

Ni1000 

Enter X1 sensor calibration offset (Ni or Pt only) 

±

  5 K 

0 K 

Enter X1 active sensor range (0 to 10 Vdc only) 

-100 to 2400 

32°F to 122°F 
(0°C to 50°C) 

 

 

 

Select auxiliary sensor X2  

Ni1000, Pt1000, 0 to 10 Vdc 

Ni1000 

Enter X2 sensor calibration offset (Ni or Pt only) 

±

  5 K 

0 K 

Enter X2 active sensor range (0 to 10 Vdc only) 

-100 to 2400 

32°F to 122°F 
(0°C to 50°C) 

 

 

 

Select sensor X3 (for Economizer sensor) 

Ni1000, Pt1000, 0 to 10 Vdc 

Ni1000 

Enter X3 sensor calibration offset (Ni or Pt only) 

±

  5 K 

0 K 

Enter X3 active sensor range (0 to 10 Vdc only) 

-100 to 2400 

32°F to 122°F 
(0°C to 50°C) 

 

 

 

Select unit  for X3 (for Independent control sensor) 

C, F, %,  -----, or  
X1 32°F to 122°F (0°C to 
50

°

C) 

 Y1 (0 to 10 Vdc) 

Select X3 sensor  

Ni1000, Pt1000, 0 to 10 Vdc 

Ni1000 

Enter X3 sensor calibration offset (Ni or Pt only) 

±

  5 K 

0 K 

Enter X3 active sensor range (0 to 10 Vdc only) 

-100 to 2400 

32°F to 122°F 

 

PS 3 – Digital, Auxiliary Function, Eco and Ind. (Y) 

Range/Type 

Default 

Select digital input D1 

D/N, Filter Alarm, Alarm, on/off 

Depends on #x 

 

 

 

Aux. Function = Setpoint reset 

 

 

    Setpoint reset start point, reverse acting 

 
Setpoint reset sensor range 

 
72°F (22°C) 

    Setpoint reset end point, reverse acting  

 
Setpoint reset sensor range 

 
64°F (18°C) 

    Setpoint reset shift  

 
Setpoint reset sensor range 

 
4K 

    Setpoint reset start point, direct acting 

 
Setpoint reset sensor range 

 
82°F (28°C) 

    Setpoint reset end point, direct acting 

 
Setpoint reset sensor range 

 
90°F (32°C) 

    Setpoint reset shift 

 
Setpoint reset sensor range 

 
4K 

 

Aux. function = WIN SUM analog 

 

 

Enter changeover setpoint for winter 

Sensor range 

72°F (22°C) 

Enter changeover setpoint summer 

Sensor range 

82°F (28°C) 

Enter changeover time delay, winter 

 summer 

00.01 to 23 Hrs 59 min 

00.01 

Содержание RWD45U

Страница 1: ...dulating 0 to 10 Vdc output Universal input X1 for the main temperature sensor Universal input X2 for the following auxiliary functions On Off Standby Setpoint reset Remote setting unit Sensor averaging Alarm Winter Summer setpoint changeover Filter alarm Sensor select Universal input X3 for the following functions Economizer Second independent loop Digital input D1 for the following digital funct...

Страница 2: ... Cr Compressor RV Reversing valve Eco Economy Main Loop RV RV Auxiliary Loop 4 2H2C Eco Heat 5 3Cr RV cool Eco Heat 6 3Cr RV Heat Eco Heat x0 Standby 40 50 60 x1 Remote setpoint 41 51 61 x2 Alarm 42 52 62 x3 Filter alarm 43 53 63 x4 Setpoint reset 44 54 64 x5 Avg X1 X2 45 55 65 x6 Win Sum Digital N A N A N A x7 Win Sum Analog N A N A N A x8 Sensor select 48 58 68 x9 Active input 49 59 69 H Heating...

Страница 3: ...co 14 24 34 Setpoint Reset Main Setpoint reset Eco cool Standby 44 54 64 Setpoint Reset Main Setpoint reset Eco heat x5 Avg X1 X2 Main Main Eco x6 Win Sum Digital N A N A N A x7 Win Sum Analog N A N A N A x8 Sensor select Main Main Eco x9 Active input Main Standby Eco For applications 14 24 and 34 the X2 sensor outside air temperature is used for both economizer and setpoint reset shift Applicatio...

Страница 4: ...g Stage 2 C2 Eco Cool 40 through 49 Eco Heat 70 through 79 Ind Application Numbers Q1 Q2 Q3 Q4 Y1 20 through 29 Reversing Valve RV Cool Compressor Stage 1 Cr1 Compressor Stage 2 Cr2 Compressor Stage 3 Cr3 Eco Cool 30 through 39 Reversing Valve RV Heat 50 through 59 Reversing Valve RV Cool Eco Heat 60 through 69 Reversing Valve RV Heat 80 through 89 Reversing Valve RV Cool Ind 90 through 99 Reversi...

Страница 5: ...s cooling C Celsius scale Indicates heating F Fahrenheit scale SP h Setpoint on the heating side for temperature control No unit e g pressure air quality and air volume flow SP c Setpoint on the cooling side for temperature control K Kelvin Y1 Analog output 0 to 10V Percentage scale Q Digital outputs Output status Off ECO Economy mode Output status On R V Reversing valve status On Standby mode OFF...

Страница 6: ... sensor 0 to 10 Vdc 100 to 2400 X3H Stop point of the X3 for 0 to 10 Vdc only 100 to 2400 X3 0 10 X3 is 0 to 10 Vdc input sensor 0 to 10 Vdc 100 to 2400 X2SP Remote setpoint 0 to 10 Vdc or 0 to 1000 Ω X3 If X3 is independent control C F no unit display X1 0 to 50 C Y1 0 to 10 Vdc X2VR Variable Resistor 0 to 1000 Ω PS 1 Application Number Selection Standby mode AVERAGE Averaging sensor X1 and X2 RE...

Страница 7: ...Pt1000 0 to 10 Vdc Ni1000 Enter X2 sensor calibration offset Ni or Pt only 5 K 0 K Enter X2 active sensor range 0 to 10 Vdc only 100 to 2400 32 F to 122 F 0 C to 50 C Select sensor X3 for Economizer sensor Ni1000 Pt1000 0 to 10 Vdc Ni1000 Enter X3 sensor calibration offset Ni or Pt only 5 K 0 K Enter X3 active sensor range 0 to 10 Vdc only 100 to 2400 32 F to 122 F 0 C to 50 C Select unit for X3 f...

Страница 8: ... 1 2 and 3 0 to 4 096 s 0 s Enter min Off time for output stage 1 2 and 3 0 to 4 096 s 60 s Enter time delay TD for next stage On 0 to 4 096 s 30 s Enter changeover time delay TD heating cooling demand 0 to 4 096 s 120 s Setpoint Mode Range Type Default Enter SP h1 Sensor range 70 F 21 C Enter SP h2 Sensor range 68 F 20 C Enter SP h3 Sensor range 66 F 19 C Enter SP c1 Sensor range 73 F 23 C Enter ...

Страница 9: ...hanging Setpoint in Main Display On entering any of the setpoint displays the setpoint on display can be adjusted by pushing the SEL λ button Increase value by pressing the button or decrease the value by pressing the button When the required value is reached press the SEL λ button to save the new value Time out For setpoint adjustment during normal operation the controller will exit the setting a...

Страница 10: ...ng parameters Software Tool Optional Commissioning A software tool for the controller application selection and parameter adjustment is available It is a user friendly Windows 95 or later based software tool The software tool has the following functions Adjusting all available parameters Uploading and downloading the program Saving parameter settings Viewing or providing a print out of the setting...

Страница 11: ...1 Compressor stage 2 Compressor stage 3 Reversing valve relay Equipment with 0 to 10 Vdc input Damper actuators Room temperature sensor Auxiliary sensor or a digital input Economy or 2nd loop sensor Switch or time clock Personal computer For a single compressor CR2 and CR3 are not connected For a dual compressor CR3 is not connected Figure 5 Applications 20 through 39 50 through 69 and 80 through ...

Страница 12: ...re tightened before final mounting to front panel D Inside the ARG62 21 WARNING There must be a minimum of 0 31 inches 8 mm distance from terminations to panel enclosures to avoid electric shock Electrical Installation Notes Standard cables can be used for the controller However when mounting in an environment greatly exposed to EMI use only shielded cables The RWD45U is designed for 24 Vac operat...

Страница 13: ... product or company names mentioned herein may be the trademarks of their respective owners 2009 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 129 409 Printed in the ...

Отзывы: