background image

 

 

 
 

 
 

RWD Controllers 

Application Guide

Quick Reference

Document No. 125-3511

March 28, 2005

 

RWD44U/45U/62U/68U/82U 

 

 

The RWD Controllers have standard, pre-configured applications. The respective application and setting parameters 
are entered via push buttons on the controller or a software tool. See the individual 

Application Guides 

(available 

online)

 

or the 

Installation and Commissioning Guide

 for additional information. Use Tables 1 through 12 to determine 

the appropriate controller model and application number. 

Example:

 Select an application that controls two stages of electric heat and two stages of digital cooling, and 

includes remote setpoint and an alarm to signal dirty air filters. 

1.  Select a controller based on the number of outputs and characteristics required. In this example, four digital 

outputs are required. Select the RWD44U Controller (see Table 1). 

Table 1.  Controller Models. 

Outputs 

Controller Model 

Analog 0 to 10 Vdc 

Digital 

RWD82U 0 

RWD62U 

2 0 

RWD68U 1 

RWD44U 0 

RWD45U 1 

 

2.  Determine the main control loop. Select an application number based on the output characteristics. For the 

RWD44U Controller, main control loop 1X (application group 10 through 19) contains the output characteristics 
that match this example (see Table 3). 

3.  Determine the auxiliary control loop. In this example, an auxiliary control loop (X1) is required to readjust the 

setpoint remotely (see Table 4).  

The controller model and application number needed for this example is 

RWD44U, Application #11

Table 2.  Legend. 

 

Digital Output (DO) 
cooling 

RV

Reversing valve cooling 

 

Analog control loop, DA 

 

Digital Output (DO) 
heating 

RV

Reversing valve heating 

 

Analog control loop, RA 

Siemens Building Technologies, Inc. 

Содержание RWD Series

Страница 1: ...nd characteristics required In this example four digital outputs are required Select the RWD44U Controller see Table 1 Table 1 Controller Models Outputs Controller Model Analog 0 to 10 Vdc Digital RWD82U 0 2 RWD62U 2 0 RWD68U 1 1 RWD44U 0 4 RWD45U 1 4 2 Determine the main control loop Select an application number based on the output characteristics For the RWD44U Controller main control loop 1X ap...

Страница 2: ...t Configurations X1 X2 and D1 Applications 10 Through 39 D1 Options X1 X2 Filter Alarm Alarm Day Night Standby x0 Standby Main Standby x1 Remote setpoint Main Remote setpoint x2 Alarm Main Alarm x3 Filter alarm Main Filter alarm x4 Comp Shift Main Compensation x5 Avg X1 X2 Main Main x6 Win Sum Digital Main Win Sum x7 Win Sum Analog Main Win Sum x8 Sensor select Main Main x9 Active input Main Stand...

Страница 3: ...C Eco Heat 5x 3 stage Cr RV cool Eco Heat 6x 3 stage Cr RV heat Eco Heat x0 Standby 40 50 60 x1 Remote setpoint 41 51 61 x2 Alarm 42 52 62 x3 Filter alarm 43 53 63 x4 Comp shift 44 54 64 x5 Avg X1 X2 45 55 65 x6 Win Sum Digital N A N A N A x7 Win Sum Analog N A N A N A x8 Sensor select 48 58 68 x9 Active input 49 59 69 Main Loop H Heating C Cooling Cr Compressor RV Reversing valve Ind Independent ...

Страница 4: ...Win Sum Digital N A N A N A x7 Win Sum Analog N A N A N A x8 Sensor select Main Main Eco x9 Active input Main Standby Eco For Applications 14 24 and 34 the X2 sensor outside air temperature is used for both economizer and compensation shift Applications 70 Through 99 D1 Options X1 X2 X3 Filter Alarm Alarm Day Night Standby x0 Standby Main Standby Ind x1 Remote setpoint Main Remote setpoint Ind x2 ...

Страница 5: ...cation Numbers Main Loop H Heating C Cooling SP Setpoint First digit Main control loop Second digit Auxiliary control loop SP SP SP SP SP SP Auxiliary Loop 1 H Sequence 2 H H Sequences 3 H C Sequences 4 C Sequence 5 C C Sequences x0 No auxiliary 10 20 30 40 50 x1 Remote setpoint 11 21 31 41 51 x2 Absolute limiter 12 22 32 42 52 x3 Relative limiter 13 23 33 43 53 x4 Comp shift 14 24 34 44 54 x5 Cas...

Страница 6: ...oling sequence output is set to Direct Acting default This is typically used for normally closed valves Output can be set to reverse acting by changing the MIN and MAX value Table 11 RWD82U Controller Application Numbers H Heating C Cooling 3P 3 position 1st digit Main Control Loop 2nd digit Auxiliary Control Loop Main Loop Auxiliary Loop 1x H H Dependent 2x H H Independent 3x H 3 Position 4x H C ...

Страница 7: ...ve explanation x MAX Value to start Limiter cooling x x MIN Value to start Limiter heating x x XP h P band in Limiter heating x x XP c P band in Limiter cooling x x TN h Integrating time heating x x x TN c Integrating time cooling x x x COMP start point heating reverse acting x COMP end point heating reverse acting x Adjustment in heating reverse acting x COMP start point cooling direct acting x C...

Отзывы: