43/69
Siemens Building Technologies
Electronic Air / Fuel Ratio Control System
CC1P7873.1en
HVAC Products
15 Programming the RVW26...
15.10.2002
The setting choices of the RVW26... are assigned to programming levels.
Each programming level represents a display window of the AZW20.20.
The programming level can be changed by pressing buttons
Ü
/
Þ
.
There is a total of 9 programming levels available:
D ata transfer
7
Fault proto col
F
Ignition position
(Fuel 1)
Ignition position
(Fuel 2)
C urve
characteristics
(Fuel 1)
78 73 1b 01e/10 02
5
5
C urve
characteristics
(Fuel 2)
6
6
Functions
(Fuel 1)
Functions
(Fuel 2)
4
4
System configuration 2
3
Measuring
end switches
(Fuel 1)
2
2
Measuring
end switches
(Fuel 2)
System configuration 1
1
Operating mode
0
F
7
6
5
4
3
2
1
0
Fig. 23
Structure of the programming levels
Within each programming level, buttons «
D
» and «
Ñ
» are used to select the required
parameter.
Buttons «+» and «-» are used to change the selected parameters.
The first column on the display continuously indicates the current programming level,
the program phase of the RVW26..., and the type of fuel currently burnt.
It should be noted that a number of parameters must be set separately for each type for
fuel.
The type of fuel cannot be selected with the handheld unit. This must be done exter-
nally via terminals «F1» and «F2».
Fig. 24 on the next page shows the display in detail.