53/94
Siemens Building Technologies
Basic Documentation RVD110, RVD130
CE1P2381E
HVAC Products
15 Function block Extra legionella functions
27.05.2004
In the case of direct d.h.w. heating without circulating pump, the set value has no im-
pact (no dwelling time).
15.1.5 Operation of circulating pump
The circulating pump can be forced to run during the period of time the legionella func-
tion is active. This ensures that hot water also circulates through the plant’s hot water
distribution system. Entry (0 or 1) is made on operating line 128.
If the storage tank temperature exceeds the legionella setpoit minus 1 K, the circulating
pump will be forced to run.
If the storage tank temperature falls below the legionella setpoint by more than
SD + 2 K (switching differential plus 2 K), the circulating pump will no longer be acti-
vated.
15.1.6 Maximum limitation of the return temperature
For details, refer to section 19.3.3 “Maximum limitation with d.h.w. heating“.
15.2 Mode of operation
Conditions for activation of the legionella function:
•
The storage tank temperature is acquired with 1 or 2 sensors (legionella function
cannot be provided when using thermostats)
•
The legionella function has been parameterized (operating line 104)
•
D.h.w. heating is switched on (button
is lit)
•
The holiday function is not active
If the criteria “Set day” and “Time” are met, the legionella function will be released.
Release of the legionella function causes the d.h.w. temperature setpoint to be raised
to the level of the legionella setpoint and to forced charging. If d.h.w. heating is swit-
ched off or the holiday function is active, the legionella function will be released. On
completion of the overriding function, d.h.w. charging to the legionella setpoint will be
triggered since the legionella function continues to be released.
The behavior of the legionella function as a function of the d.h.w. temperature is as
follows:
T
BWw
T
BWw
- SD
BW
T
BWw
- SD
BW
- 2 K
ON
OFF
ON
OFF
T
BWx
t
23
81
D
0
7
1
2
8
5
6
3
ON
OFF
4
7
①
Circulating pump
⑦
Start dwelling time
②
Forced charging
⑧
Dwelling time has elapsed
③
Release of the legionella function
T
BWx
D.h.w.
temperature
④
Start conditions for the legionella function met
T
BWw
D.h.w. temperature setpoint
⑤
Start dwelling time
SD
BW
Switching differential of d.h.w charging
⑥
Reset dwelling time
t Time