36/94
Siemens Building Technologies
Basic Documentation RVD110, RVD130
CE1P2381E
HVAC Products
11 Function block Space heating
27.05.2004
2381
B
01
H
T
Vw
s
s
T
AM
T
Rw
/ /
Generation of setpoint with weather-compensated control without room unit
*
Multiplier
Operating line 5 = setting of heating curve slope
s
Slope of heating curve
Operating line 69 = setting of heat gains
T
Rw
Room temperature setpoint
Operating line 71 = setting of parallel displacement of heating curve
T
Vw
Flow
temperature
setpoint
T
AM
Composite outside temperature
H Heating
curve
11.4.3 Setpoint of room temperature-compensated control
The setpoint is generated based on the deviation of the actual room temperature from
the setpoint. In addition, the heating curve with a fixed outside temperature of 0 °C is
taken into consideration.
23
81
B
02
E
H
T
Vw
T
Rw
/ /
+10 K
-10 K
I
+50 K
-50 K
L
T
Rx
1
/
2
1
s
s
0 °C
s
Generation of setpoint with room temperature-compensated control
*
Multiplier
Operating line 5 = setting of heating curve slope
E
Room authority
Operating line 69 = setting of heat gains
H
Heating curve
Operating line 70 = setting of room temperature influence (gain factor)
I
Integrator with limitation
Operating line 71 = setting of parallel displacement of heating curve
L Limiter
S Heating
curve
slope
T
Rw
Room temperature setpoint
T
Rx
Room
temperature
T
Vw
Flow
temperature
setpoint
11.4.4 Setpoint
of
weather-compensated control with room
temperature influence
Here, in addition to the outside temperature and the room temperature setpoint, the
heating curve and the room temperature influence act on the flow temperature setpoint.