RUGGEDCOM RS930W
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications
19
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
•
Section 4.1, “Power Supply Specifications”
•
Section 4.2, “Failsafe Relay Specifications”
•
Section 4.3, “Fiber Optic Ethernet Port Specifications”
•
Section 4.4, “Wireless Ethernet Port Specifications”
•
Section 4.5, “Operating Environment”
•
Section 4.6, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power Supply Type
Minimum
Maximum
Internal Fuse
Rating
ab
Isolation
Maximum Power
Consumption
c
88 VDC
300 VDC
4 kVAC
HI
85 VAC
264 VAC
5.5 kVDC
24
10 VDC
36 VDC
1.5 kVDC
48
36 VDC
72 VDC
3.15 A(T)
1.5 kVDC
10 W
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration.
Section 4.2
Failsafe Relay Specifications
Parameter
Value (Resistive Load)
Max Switching Voltage
30 VAC, 80 VDC
Rated Switching Current
0.3 A @ 30 VAC
1 A @ 30 VDC, 0.3 A @ 80 VDC
Isolation
1500 V
rms
d
d
Dielectric test voltage (1 minute) between coil and contacts