background image

RUGGEDCOM RS930L

Installation Guide

10/2013

Preface

Introduction

1

Installing the Device

2

Communication Ports

3

Technical Specifications

4

Dimension Drawings

5

Certification

6

Содержание RUGGEDCOM RS930L

Страница 1: ...RUGGEDCOM RS930L Installation Guide 10 2013 Preface Introduction 1 Installing the Device 2 Communication Ports 3 Technical Specifications 4 Dimension Drawings 5 Certification 6 ...

Страница 2: ...h this in mind Siemens products and solutions undergo continuous development Siemens recommends strongly that you regularly check for product updates For the secure operation of Siemens products and solutions it is necessary to take suitable preventive action e g cell protection concept and integrate each component into a holistic state of the art industrial security concept Third party products t...

Страница 3: ... the Device on a DIN Rail 6 2 1 2 Mounting the Device to a Panel 6 2 2 Connecting Power 7 2 2 1 Connecting High AC DC Power 8 2 2 2 Connecting Low DC Power 9 2 3 Connecting the Failsafe Alarm Relay 10 2 4 Connecting to the Device 11 2 5 Cabling Recommendations 12 Chapter 3 Communication Ports 13 3 1 EoVDSL Ports 13 3 1 1 EoVDSL Wiring 14 3 1 2 Configuration and Setup 15 3 1 3 EoVDSL Performance 15...

Страница 4: ...L Installation Guide iv 4 4 Mechanical Specifications 18 Chapter 5 Dimension Drawings 19 Chapter 6 Certification 21 6 1 Agency Approvals 21 6 2 FCC Compliance 21 6 3 Industry Canada Compliance 21 6 4 EMI and Environmental Type Tests 22 ...

Страница 5: ...ently hazardous situations that if not avoided will result in death or serious injury WARNING WARNING alerts describe hazardous situations that if not avoided may result in serious injury and or equipment damage CAUTION CAUTION alerts describe hazardous situations that if not avoided may result in equipment damage IMPORTANT IMPORTANT alerts provide important information that should be known before...

Страница 6: ...dge and expertise to understand the various technologies associated with critical communications network infrastructure technologies Siemens unique mix of IT Telecommunications expertise combined with domain knowledge in the utility transportation and industrial markets allows Siemens to provide training specific to the customer s application For more information about training services and course...

Страница 7: ...cation certification optional conformal coating and a galvanized steel enclosure allows the RS930L to be placed in almost any location The RS930L is packaged in a compact galvanized steel enclosure that allows either DIN or panel mounting for efficient use of cabinet space The RS930L provides an integrated power supply with a wide range of voltages 88 300 VDC or 85 264 VAC for worldwide operabilit...

Страница 8: ...al Exceeds NEMA TS 2 traffic control equipment Hazardous Location Certification Class 1 Division 2 40 to 85 C 40 to 185 F operating temperature no fans 20 AWG galvanized steel enclosure DIN or panel mounting options provide secure mechanical reliability Conformal coated printed circuit boards optional Management Tools Web based Telnet CLI management interfaces SNMP v1 v2 v3 56 bit encryption Remot...

Страница 9: ...m Indicator LED 3 RS232 Serial Console Port Power Indicator LEDs The power indicator LED illuminates when power is being supplied to the device Alarm Indicator LED The alarm indicator LED illuminates when an alarm condition exists RS232 Serial Console Port This port is for interfacing directly with the device and accessing initial management functions ...

Страница 10: ...RUGGEDCOM RS930L Installation Guide Chapter 1 Introduction Ports Controls and Indicator LEDs 4 ...

Страница 11: ...void Changes or modifications not expressly approved by Siemens AG could invalidate specifications test results and agency approvals and void the user s authority to operate the equipment IMPORTANT This product should be installed in a restricted access location where access can only be gained by authorized personnel who have been informed of the restrictions and any precautions that must be taken...

Страница 12: ...the device to a DIN rail do the following 1 Align the slot in the bracket with the DIN rail 1 1 2 Figure 2 DIN Rail Mounting 1 DIN Rail 2 DIN Rail Bracket 2 Pull the release on the bracket down and slide the device onto the DIN rail Let go of the release to lock the device in position Section 2 1 2 Mounting the Device to a Panel For panel installations the RS930L can be equipped with panel adapter...

Страница 13: ...it breaker must be installed Equipment must be installed according to applicable local wiring codes and standards All line to ground transient energy is shunted to the Surge Ground terminal In cases where users require the inputs to be isolated from ground remove the ground braid between Surge and Chassis Ground Note that all line to ground transient protection circuitry will be disabled IMPORTANT...

Страница 14: ...owing CAUTION Electrical hazard risk of damage to equipment Do not connect AC power cables to terminals for DC power Damage to the power supply may occur CAUTION Electrical hazard risk of damage to equipment Before testing the dielectric strength HIPOT in the field remove the braided ground cable connected to the surge ground terminal and chassis ground This cable connects transient suppression ci...

Страница 15: ...or all surge and transient suppression circuitry internal to the unit 4 Connect the ground terminal on the power source to the chassis ground terminal on the device Section 2 2 2 Connecting Low DC Power To connect a low DC power supply to the device do the following CAUTION Electrical hazard risk of damage to equipment Before testing the dielectric strength HIPOT in the field remove the braided gr...

Страница 16: ...ion circuitry internal to the unit 4 Connect the ground terminal on the power source to the chassis ground terminal on the device Section 2 3 Connecting the Failsafe Alarm Relay The failsafe relay can be configured to latch based on alarm conditions The NO Normally Open contact is closed when the unit is powered and there are no active alarms If the device is not powered or if an active alarm is c...

Страница 17: ...or terminal directly to the serial console port to access the boot time control and ROS console interface IMPORTANT The serial console port is intended to be used only as temporary connections during initial configuration or troubleshooting The serial console port implements RS232 DCE Data Communication Equipment on a DB9 connector The following is the pin out for the port 5 9 6 1 Figure 7 Serial ...

Страница 18: ...ing of any length for critical real time substation automation applications All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against damage from electrical transients and conform with IEC 61850 3 and IEEE 1613 Class 1 standards This means that during a transient electrical event communications errors or interruptions may occur but recovery is autom...

Страница 19: ...rnet Ports 10 100Base TX 7 EoVDSL Port 9 EoVDSL Port The following sections describe the available ports Section 3 1 EoVDSL Ports Section 3 1 EoVDSL Ports Ethernet over VDSL EoVDSL ports operate in pairs with one device configured as the Master and the other as the Slave In VDSL Very high bit rate Digital Subscriber Line the terms Central Office CO or Line Termination LT are used interchangeably f...

Страница 20: ...L ports the Master LED will be on all the time if the device is set to be the Master or off if the device is set to be the Slave Status LED State Description Green Solid The device is in Master mode Master Off The device is in Slave mode Green Solid Link established Green Blinking Link activity Link Act Off No link detected NOTE All RJ11 connectors conform to the standard telephony pin configurati...

Страница 21: ...eral times before setting on a final link speed and declaring the port up For more information about configuring the RS930L refer to the ROS User Guide for RS900LW RS930LW Section 3 1 3 EoVDSL Performance The EoVDSL ports can be configured to operate in one of two modes Auto Mode default and Manual Mode In Auto Mode the device will step through the different speeds and automatically select the bes...

Страница 22: ... 1600 35 15 0 60 2000 30 30 0 70 2300 25 45 0 90 3000 20 60 1 00 3300 15 75 1 30 4300 10 90 1 70 5600 5 105 2 00 6600 2 5 120 2 50 8200 1 2 150 The following performance is typical with Long Reach EoVDSL ports Distance km Distance feet Downstream Master to Slave Mbps Upstream Slave to Master Mbps Time to Achieve Port Up in Auto Mode Seconds 0 50 1600 40 20 15 1 00 3300 25 5 30 1 50 4900 20 0 54 45...

Страница 23: ...er Supply Specifications Input Range Power Supply Type Minimum Maximum Internal Fuse Rating ab Isolation Maximum Power Consumption c 88 VDC 300 VDC 4 kVAC HI 87 VAC 264 VAC 5 5 kVDC 24 10 VDC 36 VDC 1 5 kVDC 48 36 VDC 72 VDC 3 15 A T 1 5 kVDC 10 W a F denotes fast acting fuse b T denotes time delay fuse c Power consumption varies based on configuration Section 4 2 Failsafe Relay Specifications Par...

Страница 24: ...C 40 to 185 F Measured from a 30 cm 12 in radius surrounding the center of the enclosure Ambient Relative Humidity 5 to 95 Non condensing Ambient Storage Temperature 40 to 85 C 40 to 185 F Section 4 4 Mechanical Specifications Parameter Value Dimensions Refer to Chapter 5 Dimension Drawings Weight 1 2 kg 2 7 lbs Ingress Protection IP40 1 mm or 0 04 in objects Enclosure 20 AWG Galvanized Steel ...

Страница 25: ...OM RS930L Installation Guide Chapter 5 Dimension Drawings 19 Dimension Drawings NOTE All dimensions are in millimeters unless otherwise stated 65 13 116 59 187 96 168 66 7 87 99 06 Figure 10 Overall Dimensions ...

Страница 26: ...Chapter 5 Dimension Drawings RUGGEDCOM RS930L Installation Guide 20 13 64 101 60 11 18 183 89 83 82 194 06 120 65 78 74 Figure 11 Panel and DIN Rail Mount Dimensions ...

Страница 27: ...e FCC FCC Part 15 Class A Approved FDA CDRH 21 CFR Chapter I Sub chapter J Approved Section 6 2 FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equi...

Страница 28: ...er ports 4 kV line to earth 2 kV line to line 4 Signal ports 10 V 3 DC Power ports 10 V 3 AC Power ports 10 V 3 IEC 61000 4 6 Induced Conducted RFI Earth ground ports 10 V 3 IEC 61000 4 8 Magnetic Field Enclosure ports 40 A m continuous 1000 A m for 1 s DC Power ports 30 for 0 1 s 60 for 0 1 s 100 for 0 05 s IEC 61000 4 29 30 for 1 period 60 for 50 periods IEC 61000 4 11 Voltage Dips and Interrupt...

Страница 29: ...evels Enclosure Contact 8 kV C37 90 3 9 ESD Enclosure Air 15 kV C37 90 2 8 Radiated RFI Enclosure ports 35 V m Signal ports 4 kV 2 5 kHz DC Power ports 4 kV AC Power ports 4 kV Fast Transient Earth ground ports 4 kV Signal ports 2 5 kV common mode 1MHz DC Power ports 2 5 kV common and differential mode 1MHz C37 90 1 7 Oscillatory AC Power ports 2 5 kV common and differential mode 1MHz Signal ports...

Страница 30: ...ide 24 EMI and Environmental Type Tests Test Description Test Levels Severity Levels IEC 60068 2 30 Humidity Damp Heat Cyclic Test Db 95 non condensing 55 C 131 F 6 cycles IEC 60255 21 1 Vibration 2 g 10 150 Hz Class 2 IEC 60255 21 2 Shock 30 g 11 ms Class 2 ...