Technical Specifications
5.2 Failsafe Alarm Relay Specifications
5.2
Failsafe Alarm Relay Specifications
Hazardous Environments
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
1 A
80 VDC
30 VAC
0.3 A
1500 V
rms
for 1 minute
Non-Hazardous Environment
Maximum Switching Voltage
Rated Switch-
ing Current
Isolation
30 VDC
2 A, 60 W
125 VDC
0.24 A, 30 W
125 VAC
0.5 A, 62.5 W
220 VDC
0.24 A, 60 W
250 VAC
0.25 A, 62.5 W
1500 V
rms
for 1 minute
5.3
Supported Networking Standards
Standard
10 Mbps Ports
100 Mbps
Ports
1000 Mbps
Ports
Description
IEEE 802.1D
ü
ü
ü
MAC Bridges
IEEE 802.1p
ü
ü
ü
Priority Levels
IEEE 802.1Q
ü
ü
ü
VLAN (Virtual LAN) Tagging
IEEE 802.3ab
ü
1000Base-Tx
IEEE 802.3x
ü
ü
ü
Full Duplex Operation
IEEE 802.3z
ü
1000Base-LX
5.4
Copper Ethernet Port Specifications
The following details the specifications for copper Ethernet ports that can be ordered
with the RUGGEDCOM RS910.
Speed
Connector
Duplex
Cable Type
Wiring
Maximum
Isolation
10/100Base-
TX
DB9
FDX/HDX
> CAT 5
TIA/EIA
T568A/B
100 m
(328 ft)
1.5 kV
10/100Base-
TX
RJ45
FDX/HDX
> CAT 5
TIA/EIA
T568A/B
100 m
(328 ft)
1.5 kV
Auto-negotiating.
Shielded or unshielded.
Auto-crossover and auto-polarity.
28
RUGGEDCOM RS910
Installation Manual, 02/2020, C79000-G8976-1029-09