RUGGEDCOM RS416
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications
27
Technical Specifications
This section provides important technical specifications related to the device and available modules.
CONTENTS
•
Section 4.1, “Power Supply Specifications”
•
Section 4.2, “Failsafe Relay Specifications”
•
Section 4.3, “Copper Ethernet Port Specifications”
•
Section 4.4, “Fiber Optic Ethernet Port Specifications”
•
Section 4.5, “Serial Port Specifications”
•
Section 4.6, “IRIG-B Port Specifications”
•
Section 4.7, “Operating Environment”
•
Section 4.8, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power Supply Type
Minimum
Maximum
Internal Fuse
Rating
a
b
Isolation
Maximum Power
Consumption
c
12 VDC
24 VDC
10 VDC
36 VDC
6.3 A(F)
48 VDC
36 VDC
59 VDC
3.15 A(T)
1.5 kVDC
HI (125/250 VDC)
d
88 VDC
300 VDC
HI (110/230 VAC)
d
85 VAC
264 VAC
2 A(T)
4 kVAC, 5.5 kVDC
25 W
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than fiber optic ports.
d
The HI power supply is the same power supply for both AC and DC.
Section 4.2
Failsafe Relay Specifications
Maximum Switching Voltage
Rated Switching Current
30 VAC
0.3 A, 1.0 A
80 VDC
0.3
Содержание RUGGEDCOM RS416
Страница 4: ...RUGGEDCOM RS416 Installation Guide iv ...
Страница 34: ...RUGGEDCOM RS416 Installation Guide Chapter 3 Communication Ports Connecting Multiple RS485 Devices 26 ...
Страница 40: ...RUGGEDCOM RS416 Installation Guide Chapter 4 Technical Specifications Mechanical Specifications 32 ...
Страница 44: ...RUGGEDCOM RS416 Installation Guide Chapter 5 Dimension Drawings 36 ...
Страница 50: ...RUGGEDCOM RS416 Installation Guide Chapter 6 Certification EMC and Environmental Type Tests 42 ...