Siemens / Building Technologies / HVAC Products
Mounting and siting notes REA23.03RF and REA-R.03/1
1
Siting the units
1.1 REA23.03RF and REA-R.03/1
•
The units should be sited such that transmited and received
signals will be disturbed as little as possible. For this reason, the
following points should be observed with both the REA23.03RF
and REA-R.03/1:
−
Do not mount the units on metal surfaces
−
Do not mount the units near electrical wires or electronic
equipment such as PCs, TV sets, microwave equipment,
etc.
−
Do not mount the units in the vicinity of large metal
structures or other construction elements with fine metal
meshes like special glass or special concrete
•
The distance between controller/transmitter and receiver
should not exceed 20 m or 2 floors.
1.2 REA23.03RF
(controller/transmitter)
•
The controller / transmitter should be mounted in the main living
room (wall mounting according to Fig. C, free standing according
to Fig. E with stand)
•
The REA23.03RF should be located such that it can acquire the
room temperature as accurately as possible, without getting
affected by direct solar radiation or other heat or refrigeration
sources.
Siting note for wall mounting:
min.
10 cm
22
6
1Z03
1.3 REA-R.03/1
(receiver)
•
The receiver and switching unit should preferably be mounted
near the actuating device
•
Make certain that the mounting location is dry and protected
from splash water
•
The unit can be fitted to most commercially available recessed
conduit boxes or directly on the wall.
2 Check
wiring
For the electrical connections, refer to “Connection diagram“.
Note:
Do not use stranded wires, only solid wires
or stranded wires with ferrules.
3 Notes
•
The local regulations for electrical installations must be
complied with
•
If the reference room is equipped with thermostatic radiator
valves, they must be set to their fully open position
•
In the event of a power failure at the REA-R.03/1, the relay will
be deenergized.
•
If in normal operation REA-R.03/1 does receive for more than
25 minutes a very weak or no control telegram from
REA23.03RF, LED_1 starts to flash in red.
If control telegram is still understood correctly, receiver
continues with normal operation. If control telegram is not
understood anymore, relay remains in last position being
switched to before.
As soon as REA-R.03/1 does receive any correct control
telegram from REA23.03RF again, receiver continuous with
normal operation
•
In case of error, REA-R.03/1 switches off relay approximately
60 minutes after reception of last correct control telegram.
The controlled device is also switched off and LED_1 flashes
in red.
As soon as REA-R.03/1 does receive any correct control
telegram from REA23.03RF again, receiver continuous with
normal operation
Commissioning RF Set
1
Switch on REA23.03RF
•
Remove the battery transit tab (also refer to Fig. F): As soon
as the battery transit tab is removed, the unit starts to operate.
2
Mount REA-R.03/1 temporarly
•
If possible, mount receiver temporarly in a first run (e.g. double
coated tape). Doing that, location of best RF reception can be
identified later on.
See clause “5 Find location of best reception“
•
Completely wire and mount REA-R.03/1 temporarly. Proceed
according Fig. H to M (please also close front cover)
3
Link REA-R.03/1 with REA23.03RF
a) Switch on power at REA-R.03/1: LED_1 (Fig. H) lights always
in red or flashes in red
b) Press the "RESET“ button on REA-R.03/1 for about
4 seconds: The orange LED_2 (Fig. H) will flash very fast
and briefly (stored address of REA23.03RF will be erased)
c)
Press the "SET“ button (set / learn) for about 3 sec. until the
orange LED starts flashing slowly and continuously:
Receiver
is now in learning mode
d) The receiver stays max. 25 minutes in learning mode. If no
learning telegram from REA23.03RF is received during that
period of time, repeat steps b) and c) again
e) Press the ESC button
ESC
on REA23.03RF for about
4 seconds. Learning telegram is transmitted
f)
If REA-R.03/1 receives learning telegram, the orange LED_2
flashes fast and briefly
g) If the orange LED_2 is steady on, the relay is energized
(= controlled device ON)
h) If the orange LED_2 is dark, the relay is deenergized
(= controlled device OFF)
i)
Depending on the operating state, REA23.03RF repeats the
ON or OFF control telegram every 3 minutes. With this the
relay will be switched ON or OFF according to control
telegram latest after 3 minutes
j)
If REA-R.03/1 does not receive any correct control telegram
within 60 minutes, controlled device is being switched off
and LED_1 flashes in red
k)
In the event of a power failure at the REA-R.03/1, the relay will
be deenergized.
4 Site
REA23.03RF
•
Site REA23.03RF at preferred location for mounting at wall or
setting up with stand. Remove the unit from its base by
proceeding according to Fig. A:
- for wall mount, refer to Figs. B, C and D
- for set up with stand, refer to Fig. E
•
Also refer to “Mounting and siting notes REA23.03RF and
REA-R.03/1“
5
Find location of best RF reception
h) Switch off power at REA-R.03/1