51 / 68
Siemens
RDU341 Basic Documentation
CE1P3172en
Building Technologies
2015-06-08
P
a
ra
m
e
te
r
Name
Factory setting
Range
Communications
P81 Device
address
1)
255
1…255
P82
Geographical
zone
(apartment)
2)
---
---, 1...126
P83
Geographical
zone
(room)
2)
1
---, 1...63
P87
Air
distribution
zone
---
---, 1...31
P88 Transformation
Precomfort
0
0 = Economy
1 = Comfort
1)
Physical address = Area.Line.DeviceAddress. Factory setting for Area = 0, Line = 2.
Can be changed by special management service e.g. from line coupler or via ACS commissioning tool.
2)
Type = geographical zone A.R.S. In RDG RDU sub zone = fixed value 1
P
a
ra
m
e
te
r
Name
Range
Diagnostics & test
d01
Application number
NONE = (No application)
Sd = Single duct
SdEL = Single duct with electric heater
d02
X1 state
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
d03
X2 state
0 = Not activated (for DI)
1 = Activated (DI)
0…49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open