Built-in room temperature sensor
Measuring range
Accuracy at 25 °C (77 °F)
Temperature calibration range
0…49 °C (32…120 °F)
< ± 0.5 K (± 1 °F)
± 3.0 K (± 6 °F)
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C (1 °F)
0.5 °C (1 °F)
Operation
Climatic conditions
Temperature
Humidity
As per IEC 60721-3-3
Class 3K5
0...50 °C (32…120 °F)
< 95% r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 60721-3-2
Class 2K3
-
25...60 °C (
-
13…140 °F)
< 95% r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
As per IEC 60721-3-1
Class 1K3
-
25...60 °C (
-
13…140 °F)
< 95% r.h.
EU Conformity (CE)
CE1T3181xx
*)
RCM conformity
CE1T3181en_C1
*)
UL
UL 916 PAZX
CSA-C22.2 No. 205 PAZX7
Electronic control type
2.B (micro-disconnection on
operation)
Safety class
III as per EN 60730
Pollution class
Normal
Degree of protection of housing
IP30 as per EN 60529
Connection terminals
Solid wires or prepared
stranded wires
1 x 0.4…2.5 mm
2
(14 gauge)
or 2 x 0.4…1.5 mm
2
(16 gauge)
Housing front color
RAL 9003 white
Weight
0.350 kg
*)
The documents can be downloaded from
http://siemens.com/bt/download
Environmental
conditions
Standards
General