37/44
Siemens
RDG400 Basic Documentation
CE1P3182en
Building Technologies
2015-05-20
6 Engineering
6.1 Connection
terminals
G X1 M X2 D1 GND
G0
SELV
G, G0
Operating voltage AC 24 V
Y10/G0
Control output for DC 0…10 V actuator
Y1/G, Y2/G Control output for On/Off, PW M or 3-position actuators
X1, X2
Multifunctional input for temperature sensor (e.g. QAH11.1)
or potential-free switch
Factory
setting:
- X1 = external room temperature sensor
- X2 = sensor or switch for automatic heating/
cooling changeover
Change of setting: Parameters P38, P40
M
Measuring neutral for sensor and switch
D1, GND
Multifunctional input for potential-free switch.
Factory setting: Operating mode switchover contact
Change of setting: Parameter P42