Product standards
Automatic electrical controls for household
and similar use
Special requirements for temperature-
dependent controls
EN 60 730 – 1
EN 60 730 – 2 - 9
Electromagnetic compatibility
Emissions
Immunity
IEC/EN 61 000-6-3
IEC/EN 61 000-6-1
Devices of safety class
II to EN 60 730
Pollution class
normal
Degree of protection of housing
IP 30 to EN 60 529
Connection terminals
solid wires or prepared
stranded wires
2x0.4-1.5 mm
2
or 1x2.5 mm
2
Weight 0.17
kg
Color of housing front
white, RAL 9003
General
Connection terminals
L
N Q1 Q2 Q3
Y11 N
30
5
7
G
0
1
AC 230 V
L, N
Operating voltage AC 230 V
Q1
Control output “Fan speed 1 AC 230 V
Q2
Control output “Fan speed 2 AC 230 V
Q3
Control output “Fan speed 3 AC 230 V
Y11
Control output “Valve” AC 230 V (N.O.,
for normally closed valves) or output for
compressor
Connection diagrams
Application:
2-pipe fan coil units
L
N
10 A
L
B1 M
N
Q1 Q2 Q3
Y11
N
4(2)A
max.
4(2)A
max.
I II III
A
C
230 V
3
05
7
A
05
M1
Y1
N1
M1 3-speed
fan
N1
Room temperature controller
RDF310.../RDF410...
Y1 Zone
valve
Application:
Compressor
in DX type equipment
L
N
10 A
L
N
Q1 Q2 Q3
Y11
N
4(2)A
max.
4(2)A
max.
I II III
A
C
230 V
30
5
7A
06
M1
C1
N1
M1 3-speed
fan
N1
Room temperature controller
RDF310.../RDF410...
C1 Compressor
13/14
Siemens
Room Temperature Controllers
N3067en
Building Technologies
01.10.2007