Document No. 129-497 

Installation Instructions  

May 18, 2011 

 

Economy Mode 

 

Siemens Industry, Inc.

 

Page 5 of 7

 

 

 

 

 

 

 

 

 
 

 

If you want to change the factory-set 
temperature setpoints (61

°

F [16°C] for heating 

and 82

°

F [28°C] for cooling), see 

Changing the 

Control Parameters 

and 

Commissioning

Important:

 

The Economy mode setpoint can be set to 0. 
This means 

OFF 

so that the controller is not 

active in Economy mode and symbol   will not 
appear. 

 

CAUTION: 

 

When turned 

OFF

, the controller will not provide 

valve control, which could result in freeze 
conditions.

 

 

 

 

4. Press the + and – buttons simultaneously, 

to show the current value of the selected 
parameter, which can be changed by 
repeatedly pressing the + or – button. 

5. Press b and – simultaneously 

again or wait 5 seconds after the last 
press of a button, to display the last 
parameter. 

6. If you wish to display and change 

additional parameters, repeat steps 3 
through 5. 

7. All changes will be stored 10 seconds after 

the last display or setting. 

8. Switch to normal operation 

 with the 

operating mode selector. 

Changing the Control Parameters 

Recalibrating the Sensor 

To optimize the control performance, a number of control 
parameters can be adjusted. Adjustments can be made 
during operation without opening the controller. 

If the room temperature displayed by the controller does 
not agree with the actual room temperature, the 
temperature sensor can be recalibrated by changing 
parameter P09. 

NOTE: 

For factory settings, see 

Commissioning

 

 

 

See 

Changing the Control Parameters

 and 

follow steps 1 through 3 to select parameter 
P09. 

With step 4, the room temperature displayed 
can now be matched to the actual room 
temperature. Each push of the + or – button 
changes the temperature by +/– 1

°

F (0.5°C) 

up to a maximum of +/- 5.5

°

F (3°C).  

With step 7, the recalibration is automatically 
stored 10 seconds after the last readjustment.

To change the parameters for: 

 

Setpoints for independent heating and cooling in 
Economy mode 

 

Setpoints for independent heating and cooling in 
Standby mode 

 

Upper and lower limit stops in Normal mode 

 

Heat/cool changeover points 

 Sensor 

calibration 

 

Heat/cool switching differentials 

 Fan 

control 

 

Dead zone between heating and cooling 
(RDF30U), 

proceed as follows: 

 

 

 

 
 
 
 

 

 

 

1. Set operating mode selector to Standby.

 

2. Press the + and – buttons simultaneously 

for a minimum of 3 seconds and a 
maximum of 5 seconds. Release them and 
within 2 seconds, press the + button again 
for 3 seconds. The display will show “P01”.

3. Select the required parameter by 

repeatedly pressing the + or – button: 

       

P01

P02

P20

P23

-

-

3055z01

 

 

Содержание RDF10U

Страница 1: ...pe fan coil units RDF20U Two pipe fan coil units with electrical heater RDF30U Four pipe fan coil units RDF50 1U Two pipe fan coil units with 0 to 10 Vdc output Required Tools Small flat blade screwdriver Wire strippers Electric drill Expected Installation Time 30 minutes Accessories 141 570 Lockable Thermostat Guard ARG70 Wall Plate Adapter QAH11 1 Remote Changeover Sensor Installation Step 1 Loo...

Страница 2: ...ur pipe system TH0899R1 S1 M1 Y1 I II III SN SP SN 1 3 7 8 D1 GND 4 2 10 11 12 N1 9 B2 B1 5 Figure 1 RDF10U TH0897R1 S1 B1 M1 Y1 I II III SN SP SN 1 3 9 8 D1 GND 4 2 10 11 12 N1 Y2 6 5 Figure 2 RDF30U Terminal Position RDF10U and RDF30U Terminal Function 1 Operating voltage 24 Vac negative 2 Operating voltage 24 Vac negative 3 Operating voltage 24 Vac positive 4 Heating cooling output NO 5 Heating...

Страница 3: ...ND Signal input for potential free operating mode changeover switch TH0896R1 S1 B2 M1 Y1 I II III SN SP SN 5 7 2 3 D1 Siemens Industry Inc Page 3 of 7 G 1 6 N1 10 11 12 ND B1 4 Figure 4 RDF50 1U 3 2 T F 3 2 3 2 T 3 2 QAH11 1 T F T F TH0890R1 Figure 5 RDF50 1U Terminal Position RDF50 1U Terminal Function 1 0 to 10 Vdc output for valve 2 Heat Cool changeover sensor 3 Measuring neutral 4 Return air s...

Страница 4: ...t is made The display will then stop flashing Changing from Heating to Cooling Mode Automatic changeover Display shows that heating valve is open Display shows that cooling valve is open Selecting the Three Fan Speeds with the Operating Mode Selector High Medium Low Changing from Heating or Cooling Mode to Standby With all RDF types the operating mode selector is used to manually change from Heati...

Страница 5: ... be adjusted Adjustments can be made during operation without opening the controller If the room temperature displayed by the controller does not agree with the actual room temperature the temperature sensor can be recalibrated by changing parameter P09 NOTE For factory settings see Commissioning See Changing the Control Parameters and follow steps 1 through 3 to select parameter P09 With step 4 t...

Страница 6: ...Fan control is temperature dependent in all operating modes 2 Temperature or setpoint display Room or return air temperature display Setpoint display 3 Operating action of switch for external operating mode changeover Changeover is activated when switch is closed NO Changeover is activated when switch is open NC RDF20U 4 Electrical heater Active in cooling mode Inactive in cooling mode 1 Fan contr...

Страница 7: ...alibration 0 0 K 3 K to 3 K 5 5 F to 5 5 F Not adjustable display only P10 Switching differential in heating mode 2 K 3 6 F 1 F to 7 F 0 5 K to 4 K x Not adjustable no display P11 Switching differential in cooling mode 1 K 1 8 F 1 F to 7 F 0 5 K to 4 K Integration time 5 minutes 1 to 10 minutes X X X P12 Dead zone in normal operation 2 K 3 6 F 1 F to 18 F 0 5 K to 10 K X X X P13 Active temperature...

Отзывы: