Document No. 129-497 

Installation Instructions  

May 18, 2011 

 

S1

B2

B1

M1

Y1

I

II

III

SN

SP

SN

1

3

9

8

7

D1

GND

4

2

10

11

12

N1

E1

6

5

TH0901R1

 

Figure 3.  RDF20U. 

Terminal 

Position 

RDF20U Terminal Function 

Ground for control signal 

Operating voltage 24 Vac 
negative 

Operating voltage 24 Vac 
positive 

Heating/cooling output NO 

Heating/cooling output NC 

Electric heater output NO 

Heat/Cool changeover sensor 

8 Measuring 

Neutral 

Remote air sensor 

10,11, 12 

Fan speed output III, II, I 

D1, 

GND 

Signal input for potential-free 
operating mode changeover 
switch 

 

TH0896R1

S1

B2

M1

Y1

I

II

III

SN

SP

SN

5

7

2

3

D1

Siemens Industry, Inc.

 

Page 3 of 7

 

G

1

6

N1

10

11

12

ND

B1

4

 

Figure 4.  RDF50.1U. 

 

 

3

2

T  F

3

2

3

2

T

3

2

QAH11.1

T  F

T  F

TH0890R1

 

Figure 5.  RDF50.1U. 

 

Terminal 

Position 

RDF50.1U 
Terminal Function 

0 to 10 Vdc output for valve 

Heat/Cool changeover sensor 

3 Measuring 

neutral 

Return air sensor 

Operating voltage 24 Vac, 
negative 

Operating voltage 24 Vac, 
negative 

Operating voltage 24 Vac 
positive 

10,11,12 

Fan speed output III, II, I 

D1, 

GND 

Signal input for potential-free 
operating mode changeover 
switch 

 

 

 

T  F

7

8

7

8

7

8

T

7

8

QAH11.1

T  F

T  F

TH0900R1

 

Figure 7.  RDF10U, and 

RDF20U.

 

 

 

 

Содержание RDF10U

Страница 1: ...pe fan coil units RDF20U Two pipe fan coil units with electrical heater RDF30U Four pipe fan coil units RDF50 1U Two pipe fan coil units with 0 to 10 Vdc output Required Tools Small flat blade screwdriver Wire strippers Electric drill Expected Installation Time 30 minutes Accessories 141 570 Lockable Thermostat Guard ARG70 Wall Plate Adapter QAH11 1 Remote Changeover Sensor Installation Step 1 Loo...

Страница 2: ...ur pipe system TH0899R1 S1 M1 Y1 I II III SN SP SN 1 3 7 8 D1 GND 4 2 10 11 12 N1 9 B2 B1 5 Figure 1 RDF10U TH0897R1 S1 B1 M1 Y1 I II III SN SP SN 1 3 9 8 D1 GND 4 2 10 11 12 N1 Y2 6 5 Figure 2 RDF30U Terminal Position RDF10U and RDF30U Terminal Function 1 Operating voltage 24 Vac negative 2 Operating voltage 24 Vac negative 3 Operating voltage 24 Vac positive 4 Heating cooling output NO 5 Heating...

Страница 3: ...ND Signal input for potential free operating mode changeover switch TH0896R1 S1 B2 M1 Y1 I II III SN SP SN 5 7 2 3 D1 Siemens Industry Inc Page 3 of 7 G 1 6 N1 10 11 12 ND B1 4 Figure 4 RDF50 1U 3 2 T F 3 2 3 2 T 3 2 QAH11 1 T F T F TH0890R1 Figure 5 RDF50 1U Terminal Position RDF50 1U Terminal Function 1 0 to 10 Vdc output for valve 2 Heat Cool changeover sensor 3 Measuring neutral 4 Return air s...

Страница 4: ...t is made The display will then stop flashing Changing from Heating to Cooling Mode Automatic changeover Display shows that heating valve is open Display shows that cooling valve is open Selecting the Three Fan Speeds with the Operating Mode Selector High Medium Low Changing from Heating or Cooling Mode to Standby With all RDF types the operating mode selector is used to manually change from Heati...

Страница 5: ... be adjusted Adjustments can be made during operation without opening the controller If the room temperature displayed by the controller does not agree with the actual room temperature the temperature sensor can be recalibrated by changing parameter P09 NOTE For factory settings see Commissioning See Changing the Control Parameters and follow steps 1 through 3 to select parameter P09 With step 4 t...

Страница 6: ...Fan control is temperature dependent in all operating modes 2 Temperature or setpoint display Room or return air temperature display Setpoint display 3 Operating action of switch for external operating mode changeover Changeover is activated when switch is closed NO Changeover is activated when switch is open NC RDF20U 4 Electrical heater Active in cooling mode Inactive in cooling mode 1 Fan contr...

Страница 7: ...alibration 0 0 K 3 K to 3 K 5 5 F to 5 5 F Not adjustable display only P10 Switching differential in heating mode 2 K 3 6 F 1 F to 7 F 0 5 K to 4 K x Not adjustable no display P11 Switching differential in cooling mode 1 K 1 8 F 1 F to 7 F 0 5 K to 4 K Integration time 5 minutes 1 to 10 minutes X X X P12 Dead zone in normal operation 2 K 3 6 F 1 F to 18 F 0 5 K to 10 K X X X P13 Active temperature...