3/3
Operating Instructions
CB1B1424en_01 / 2013-07-05
Siemens Building Technologies
Do you want to change parameters?
+
–
If you want to change control
parameters, proceed as follows:
•
Press
+
and
–
simultaneously for 5
seconds
•
Release the buttons and parameter
P02 is displayed
•
Press
+
or
–
to scroll to the
parameter that needs to be changed
•
Press
to select the parameter
•
Press
+
or
–
to change
the value
•
Press
to confirm and save the
changed value
•
Select and change other parameters
•
The program automatically returns to
the normal screen after a timeout
Parameter list
Parameter no. Description
Setting range
(default)
P02
Selection of °C or
°F
1 = °C (default)
2 = °F
P03
Standard
temperature
display
1 = room
temperature (default)
2 = setpoint
P04
Temperature
sensor calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P05
Comfort setpoint
5…35 °C, step 0.5
°C
(41…95 °F, step 1 °F)
Default: 20 °C, 68 °F
P06
Comfort setpoint
lock
0 = OFF (default)
1 = ON
locked
according to setting
in P05
P07
Economy setpoint 5…35 °C, step 0.5
°C
(41…95 °F, step 1 °F)
Default: 16 °C, 61 °F
P08
Economy setpoint
lock
0 = OFF (default)
1 = ON
locked
according to setting
in P07
P09
Buzzer
0 = OFF
1 = ON (default)
P10
Show frost
protection icon
0 = OFF (default)
1 = ON and always
on at 5 ºC
P19
Sequential
number of room
unit
0 = no display of
zone (RF off)
1 = zone number 1
(for standard RF)
(default)
…
6 = zone number 6
P20
RF learn
0 = OFF (default)
1 = ON
P21
Scanning rate for
the capacitive
buttons
Note: Shorter
scanning rate
means shorter
battery life
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22
Reload factory
settings
0 = OFF (default)
1 = reload
P23
Software version
information
No adjustment
possible
Receiver’s LED indication
State of receiver
State of LED
Power up (or reset)
The red and green LEDs flash
alternately for 5 seconds, then
change to constantly red.
Note: If the receiver was
previously programmed, it
shows immediately constantly
red.
Learning mode
Successful learning
mode
The red and green LEDs flash
alternately.
If RCR100RF learning is
successful, the green LED will
flash for 10 minutes.
Signal ok and
output status
change
The green LED is constantly lit,
and if the output status
changes, the green LED flashes
for 3 seconds, then changes
back to constantly green.
Fail to receive
wireless data
If the RCR100RF fails to
receive wireless data, the red
LED will start to flash after 125
minutes.
If the RCR100RF signal is
recovered, it will return to the
previous LED state.