Do you want to change parameters? 


– 

 

If you want to change control 

parameters, proceed as follows: 

  Press 

+

 

and

 

 

simultaneously for 5 

seconds 

  Release the buttons and parameter 

P02 is displayed 

  Press 

+

 or 

 

to scroll to the 

parameter that needs to be changed 

  Press 

 to select the parameter  

  Press 

+

 or 

 

to change

 

the value  

  Press 

 to confirm and save the 

changed value  

  Select and change other parameters 

  The program automatically returns to 

the normal screen after a timeout 

Parameter list 

Parameter no.  Description 

Setting range 

(default) 

P02 

Selection of °C or 

°F 

1 = °C (default)  
2 = °F 

P03 

Standard 

temperature 

display 

1 = room 

temperature (default)  
2 = setpoint  

P04 

Temperature 

sensor calibration 

-3…3 °C 
Step 0.5 °C 
(-6…6 °F, step 1 °F) 
Default: 0 °C 

P05 

Comfort setpoint 

5…35 °C, step 0.5 

°C  
(41…95 °F, step 1 °F) 
Default: 20 °C, 68 °F 

P06 

Comfort setpoint 

lock 

0 = OFF (default) 
1 = ON 

 locked 

according to setting 

in P05 

P07 

Economy setpoint  5…35 °C, step 0.5 

°C  
(41…95 °F, step 1 °F) 
Default: 16 °C, 61 °F 

P08 

Economy setpoint 

lock 

0 = OFF (default) 
1 = ON 

 locked 

according to setting 

in P07 

P09 

Buzzer 

0 = OFF 
1 = ON (default) 

P10 

Show frost 

protection icon 

0 = OFF (default) 
1 = ON and always 

on at 5 ºC 

P19 

Sequential 

number of room 

unit 

0 = no display of 

zone (RF off) 
1 = zone number 1 

(for standard RF) 

(default) 
… 
6 = zone number 6  

P20 

RF learn 

0 = OFF (default) 
1 = ON 

P21 

Scanning rate for 

the capacitive 

buttons  
Note: Shorter 

scanning rate 

means shorter 

battery life 

0.2 = 0.25 s 
0.5 = 0.5 s 
1.0 = 1.0 s (default) 
1.5 = 1.5 s  
 

P22 

Reload factory 

settings 

0 = OFF (default) 
1 = reload 

P23 

Software version 

information 

No adjustment 

possible 

Receiver’s LED indication 

State of receiver 

State of LED 

Power up (or reset) 

The red and green LEDs flash 

alternately for 5 seconds, then 

change to constantly red. 
Note: If the receiver was 

previously programmed, it 

shows immediately constantly 

red. 

Learning mode 
 

Successful learning 

mode  

The red and green LEDs flash 

alternately. 
If RCR100RF learning is 

successful, the green LED will 

flash for 10 minutes. 

Signal ok and 

output status 

change 

The green LED is constantly lit, 

and if the output status 

changes, the green LED flashes 

for 3 seconds, then changes 

back to constantly green. 

Fail to receive 

wireless data 

If the RCR100RF fails to 

receive wireless data, the red 

LED will start to flash after 125 

minutes. 
If the RCR100RF signal is 

recovered, it will return to the 

previous LED state. 

 

 