Room temperature controller

CE1N3023en

Building Technologies

2017-11-14

Accessories

Description

Type reference

Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes

ARG70

Adapter plate   96 x 120 mm for 2“ x 4“ conduit boxes

ARG70.1

Adapter plate for surface wiring 112x130 mm

ARG70.2

Engineering notes

Mounting location: on the wall or inside the fan coil unit. Not in niches or bookshelves,
not behind curtains, above or near heat sources and not exposed to direct solar radia-
tion. Mounting height is about 1.5 m above the floor. The connecting wires can be run
to the controller from a recessed conduit box.

Check the settings of the DIP switches no.1 through no.6 and change them if required.
If setpoint limitation is required, use the minimum and maximum limitation facility (en-
ergy saver).
After applying power, the controller makes a reset during which the fan LED flashes,
indicating that the reset has been correctly made. This takes about 3 seconds. Then,
the controller will be ready to operate and the LED stops flashing,

  The cables used must satisfy the insulation requirements with regard to

mains potential.

  Sensor input B1-M carries mains potential. If the sensor’s cables must be extended,

the cables used must be suited for mains voltage

Warning!
No internal line protection for supply lines to external consumers

(Q1, Q2, Q3, Y11, Y12)

Risk of fire and injury due to short-circuits!

  Adapt the line diameters as per local regulations to the rated value of the installed

overcurrent protection device.

The controller is supplied with Mounting Instructions.

Disposal

The device is considered an electronic device for disposal in terms of the Euro-
pean Directive 2012/19/EU and may not be disposed of as domestic garbage.

  Dispose of the device through channels provided for this purpose.

  Comply with all local and currently applicable laws and regulations.

Mounting, installation

and commissioning
notes

Содержание RCC30

Страница 1: ...rating voltage AC 230 V Use Typical use Control of the room temperature in individual rooms that are heated or cooled with four pipe fan coil units For opening or closing a valve for switching a three speed fan Functions The controller acquires the room temperature with its integrated sensor or external room temperature sensor QAA32 or external return air temperature sensor QAH11 1 if used and mai...

Страница 2: ...when 1 the measured room temperature lies by half the switching differential above the setpoint and 2 the heating valve has been fully open for more than one minute The cooling valve receives the OPEN command via control output Y21 when 1 the measured room temperature lies by half the switching differential plus the dead zone above the setpoint x w xdz SDC and 2 the cooling valve has been closed f...

Страница 3: ...witch no 4 in position ON standby is locked also which means that the controller will not switch to standby but to OFF In energy saving mode the setpoint of heating is 16 C and the setpoint of cooling 28 C independent of the position of the setpoint knob This operating mode will be activated when input D1 for operating mode changeover is active and DIP switch no 2 is set to ON A changeover switch ...

Страница 4: ... limitation in increments of 1 K 5 Room temperature setpoint knob 6 Set of DIP switches DIP switch no Meaning Position ON Position OFF 1 Fan control Fan control is temperature dependent in all operating modes Fan control in normal operation is tem perature independent 1 2 Operating mode change over via external switch Changeover between normal operation and energy saving mode Changeover between no...

Страница 5: ...ing which the fan LED flashes indicating that the reset has been correctly made This takes about 3 seconds Then the controller will be ready to operate and the LED stops flashing The cables used must satisfy the insulation requirements with regard to mains potential Sensor input B1 M carries mains potential If the sensor s cables must be extended the cables used must be suited for mains voltage Wa...

Страница 6: ... differential in cooling mode SDC selectable 0 5 K or 2 K Dead zone in normal operation 2 K or 5 K Setpoint Energy saving mode heating 16 C Setpoint Energy saving mode cooling 28 C Setpoint Standby 8 C Operation Climatic conditions Temperature Humidity to IEC 60721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC 60721 3 2 class 2K3 25 70 ...

Страница 7: ...r M Measuring neutral Return air temperature sensor D1 GND Status input for potential free operating mode changeover switch operating action can be selected Q1 Control output Fan speed I AC 230 V Q2 Control output Fan speed II AC 230 V Q3 Control output Fan speed III AC 230 V Y11 Control output Valve AC 230 V Y21 Control output Valve AC 230 V Connection diagram B1 Return air temperature sensor QAH...

Страница 8: ...ogies Division International Headquarters Gubelstrasse 22 CH 6300 Zug Tel 41 58 724 24 24 Siemens Switzerland Ltd 2002 2017 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies Dimensions 96 6 114 15 42 8 3021M01 90 4 4 3021M02 28 28 28 28 26 30 35 30 11 8 104 4 unit baseplate ...

Отзывы: