Technical Instructions 

RCC10U Room Temperature Controller 

Document Number 155-712 

for Two-pipe Fan Coil Units 

September 27, 2007 

Page 8 

 

Siemens Industry, Inc. 

 

Installation 
Instructions 

4-inch × 4-inch Electrical 
Wall Box Mounting 

An ARG70 wall plate adapter is required to mount an RCC10U controller to a 4-inch × 
4-inch electrical wall box. 

1.  Loosen the screw at the bottom of the controller with a small screwdriver. 

2.  Lift the bottom of the controller from the controller base and push up to remove. 

 

 

 

 

Figure 6.  Controller Separation. 

 

3.  Fasten the wall box adapter (3) to plaster ring (2), supplied by others, using the four 

screws provided with the ARG70. 

4.  Flex adapter mask (4) and snap in place inside wall box adapter (3). 

5.  Pull wires through plaster ring (2). 

6.  Fasten controller base (5), to wall box adapter assembly (3) and (4) with the two 

screws provided. 

 

Figure 7.  4-inch × 4-inch Electrical Wall Box Installation. 

Electrical wall box 

Plaster ring 

Wall box adapter* 

* Included with ARG70 

Adapter mask* 

Controller base 

Controller 

Содержание RCC10U

Страница 1: ...c Heating Cooling changeover Operating modes Normal Energy Saving Freeze Protection and Off Operating mode changeover input for remote control Selectable control parameters Operating voltage 120 Vac Application Typical use Controlling room temperature in individual rooms that are heated or cooled with two pipe fan coil units Opening or closing a valve Switching a three speed fan Suitable for use i...

Страница 2: ...cedure as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Functions The controller measures the room temperature with its integrated sensor or external return air temperature sensor QAH11 1 if used and maintains the setpoint by delivering control commands to the two position on off valve The switching differential is adjustable it can be 2...

Страница 3: ... QAH11 1 separately for return air sensing Automatic Heating Cooling Changeover CW Chilled Water Cooling mode HW Hot Water Heating mode M Operating mode SDC Switching differential cooling SDH Switching differential heating T Room temperature Tw Water temperature W Room temperature setpoint Y Signal voltage The controller uses the water temperature measured by the changeover sensor QAH11 1 to switc...

Страница 4: ...holes around the perimeter of knob as required See Figure 2 Figure 2 Setpoint Limit Stops Operating Modes The following operating modes are available Normal Operating Mode Heating or Cooling mode with automatic changeover and with manually selected fan speed Low Medium High In Normal operation the controller maintains the adjusted setpoint Freeze Protection Mode The Freeze Protection function is a...

Страница 5: ...ating Mode Changeover Switch A changeover switch can be connected to status input D1 GND When the switch closes its contact such as caused by an open window the operating mode will change from Normal operation to Energy Saving mode if DIP Switch No 2 is set to ON or from Normal operation to Standby if DIP Switch No 2 is set to OFF If the room temperature falls below 46 F 8 C and if DIP Switch No 4...

Страница 6: ... for external operating mode changeover Changeover activated when contact of switch is closed NO 1 Changeover activated when contact of switch is open NC 4 Standby Freeze Protection function disabled Freeze Protection function enabled 5 Switching differential 2 F 1 C in Heating mode1 1 F 0 5 C in Cooling mode1 7 F 4 C in Heating mode 3 5 F 2 C in Cooling mode 1 Factory setting Construction 1 Stand...

Страница 7: ... if required After applying power the controller makes a reset during which the fan LED flashes indicating that the reset has been accomplished This takes about three seconds When the LED stops flashing the controller is ready to operate Figure 5 Acceptable Mounting Height in Inches Prior to fitting the changeover sensor apply thermal conductive paste on the pipe where the sensor is to be placed S...

Страница 8: ...iver 2 Lift the bottom of the controller from the controller base and push up to remove Figure 6 Controller Separation 3 Fasten the wall box adapter 3 to plaster ring 2 supplied by others using the four screws provided with the ARG70 4 Flex adapter mask 4 and snap in place inside wall box adapter 3 5 Pull wires through plaster ring 2 6 Fasten controller base 5 to wall box adapter assembly 3 and 4 ...

Страница 9: ...Inc Page 9 4 inch 4 inch Electrical Wall Box Mounting Continued 7 Terminate wires per wiring instructions located above the terminal block Figure 8 Wiring Termination 8 Reattach the controller to the controller base 9 Secure by tightening the screw at the bottom of the controller Figure 9 Controller Reattachment The installation is now complete ...

Страница 10: ...ler from the controller base and push up to remove See Figure 6 3 Fasten the wall box adapter 3 to plaster ring 2 supplied by others using the two screws provided 4 Flex adapter mask 4 and snap in place inside wall box adapter 3 5 Pull wires through plaster ring 2 6 Fasten controller base 5 to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Steps 7 through 9 of the 4 inch 4...

Страница 11: ...th copper 262 feet 80 m cable 16 AWG for connection to Terminals 1 3 D1 and GND Operational Data Setpoint setting range 50 F to 85 F 10 C to 30 C Switching differential in Heating mode SDH 2 F or 7 F 1 C or 4 C selectable Switching differential in Cooling mode SDC 1 F or 3 5 F 0 5 C or 2 C selectable Setpoint Energy Saving mode 61 F 16 C heating Setpoint Energy Saving mode 82 F 28 C Cooling Setpoi...

Страница 12: ...Control output Valve 120 Vac 9 Control output Fan speed III 120 Vac High 10 Control output Fan speed II 120 Vac Medium 11 Control output Fan speed I 120 Vac Low D1 GND Status input for potential free operating mode changeover switch operating action can be selected Figure 11 Wiring Terminals Wiring Diagram B1 Return air temperature sensor QAH11 1 B2 Changeover sensor QAH11 1 G Operating voltage 12...

Страница 13: ...r respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 712 Printed in the USA Page 13 Dimensions Figure 13 RCC10U and Base Plate in Inches Millime...

Отзывы: