Siemens Building Technologies

CE1N2226E / 01.02.2000

Landis & Staefa Division

3/8

22

24Z

17

DIP-Switch

Reset

Temp.
Offset

If the measured room temperature does not agree with the temperature set on the knob,
the temperature detector can be recalibrated.

This can be done by adjusting a potentiometer that is located on the rear of the unit.
First, the unit must be removed from the socket.

The possible settings on the potentiometer are:

10

15

20

25

30

5

(°C)

(°C)

Pos.

22.00

20.00

8

21.75

20.00

7

21.50

20.00

6

21.25

20.00

5

21.00

20.00

4

20.75

20.00

3

20.50

20.00

2

20.25

20.00

1

20.00

20.00

0

<= Factory setting

19.75

20.00

F

19.50

20.00

E

19.25

20.00

D

19.00

20.00

C

18.75

20.00

B

18.50

20.00

A

18.25

20.00

9

After the corrections are made, the new setting must be confirmed by pressing the reset
button. Otherwise the previous settings are still active! After the reset the controller
can be remounted to the socket.

With the help of a suitable remote operation unit, the controller can be switched to the
economy temperature set for operating mode  . Changeover takes place through the
making of a potential-free contact connected to terminals T1 and T2.

The LED indicates this by being light.

After the contact opens, the selected operating mode becomes active again.

Operation according to the settings made

on the controller

Continuous economy temperature

T2

T1

22

26Z

04

T2

T1

2226Z05

Suitable remote operation units are e.g.:
– Telephone 

modem

– manual 

switch

– window 

switch

–  presence detector
– central 

unit

Calibration of detector

222

4Z04

Remote operation

Содержание RAV12 series

Страница 1: ...burners Forced draught gas and oil burners Circulating pumps in heating systems Electric direct heating Fans of electric storage heaters Zone valves normally closed PID control Self learning or selectable switching cycle Freely adjustable 24 hour mode Freely adjustable weekly mode with weekly time switch Frost protection function Minimum limitation of set point Room temperature controller AC 230 V...

Страница 2: ... inward for economy temperature Operating mode selector Heating periods according to tappet settings on time switch Continuous normal tempera ture Continuous economy tem perature Standby with frost protection Setting knob for normal temperature Setting knob for economy tempera ture LED Signalisation of override by remote control or activation of relays by switched on heating system Position for ti...

Страница 3: ...B 18 50 20 00 A 18 25 20 00 9 After the corrections are made the new setting must be confirmed by pressing the reset button Otherwise the previous settings are still active After the reset the controller can be remounted to the socket With the help of a suitable remote operation unit the controller can be switched to the economy temperature set for operating mode Changeover takes place through the...

Страница 4: ... Version 1 20 C 15 C Version 2 18 22 C 13 17 C Version 3 15 25 C 10 20 C upon request The unit has an opening for fitting a plug in type switch If desired the time switch fitted can be replaced by another The electrical connections to the controller are established via a terminal strip so that no wiring is required The time switches can only be mounted in one position The analogue time switches ar...

Страница 5: ...p of the DIP switches located at the rear of the unit If the reference room is equipped with thermostatic radiator valves they must be set to their fully open position If the measured room temperature does not agree with the set room temperature on the setting knob the detector should be recalibrated please refer to Calibration of detector Operating voltage AC 230 V conformity to EEC directive 89 ...

Страница 6: ...ion L2 N C contact AC 24 250 V T2 Signal remote operation M1 Circulating pump Y1 Regulating unit N Neutral AC 230 V T T F1 F2 N1 M1 Y2 2222S01 T T F1 F2 N1 M1 Y2 2222S02 T T Instantaneous water heater Atmospheric gas burner T N1 Y1 2222S03 M1 Circulating pump with pre control by manual mixing valve F1 Thermal reset limit thermostat N1 RAV12 room temperature controller F2 Manual reset safety limit ...

Страница 7: ...Siemens Building Technologies CE1N2226E 01 02 2000 Landis Staefa Division 7 8 138 104 37 2226M01 2226M02 Dimensions ...

Страница 8: ...CE1N2226E 01 02 2000 Siemens Building Technologies 8 8 Landis Staefa Division 1999 Siemens Building Technologies Ltd Subject to change ...

Отзывы: