Installation, Maintenance & Troubleshooting guide
| Version 04
8
Table: 20 Technical details of DOL Controller with WLC
Note: xx: Coil voltage; Z6:200-400 Vac; Z8: 260-460 Vac
yy: Coil voltage; FE:200-400V AC; FF: 260-460V AC
*Type 1 coordination as per IS/IEC 60947-4-1 Standard.
4.3: Technical details
Type
(HP /
kW)
Ie
(A)
Contactor
Relay
Range
(A)
Line
Monitoring
Relay
Recommended
Max. Back-up
HRC Fuse rating,
SIEMENS Make
type 3NA7
– 500V*
Max.
Recommended
Cu cable size
(sq:mm)
3TE7131-1HC14-1Axx
3 / 2.2
6.5
3TS3010-0Axx-08K 3US5000-1H8K
5-8
7UG0613-0yy20
20A/500V
1.5
3TE7131-1KC16-1Axx
5 / 3.7
10
3TS3110-0Axx-08K 3UW5102-1K
8-12.5
7UG0613-0yy20
25A/500V
1.5
3TE7131-2AC17-1Axx
6 / 4.5
12
3TS3210-0Axx-08K 3UW5102-2A
10-16
7UG0613-0yy20
25A/500V
1.5
3TE7131-2BC18-1Axx
7.5 / 5.5 14.5 3TS3210-0Axx-08K 3UW5102-2B
12.5-20 7UG0613-0yy20
25A/500V
2.5
3TE7131-2CC21-1Axx
10 / 7.5 19.5 3TS3311-0Axx-08K 3UW5202-2C
16-25
7UG0613-0yy20
32A/500V
2.5
Technical data:
Terminal connections:
Product
Water level controller relay
Control Voltage
415V AC
Frequency 50-60Hz
Operating modes
Single tank operation (Delivery or Suction mode)
Dual tank operation (Delivery & Suction mode)
Trip time delay
2sec (+/-0.5sec)
Water Level controller relay:
WLCA is used in the DOL Controllers for the regulation of water level in the tank.
P1:
P2:
P3:
P4:
P5:
P6:
Sensors
A1:
A2:
Coil supply
17:
18:
NO contact