11
Installation, Maintenance & Troubleshooting guide
| Version 04
Table: 20B Terminal torque values
Sr. No
Type
Size
Torque
1
3TS30..32
M4
0.8-1.4Nm
2
3TS33
M4
1.0-1.5Nm
3
Terminal block 30A
M4
0.8-1.4Nm
4
Contact block 3SB5
M3.5
0.8-1.2Nm
5
Coil Terminals A1/A2
M3.5
0.8-1.2Nm
6
Aux. terminals of all Relays
M3.5
0.8-1.2Nm
7
3UW51/52,3US50
M4
1.0-1.5Nm
8
3TX4010-2A
M3.5
0.8-1.4Nm
9
Indicating light – Amber/Green
M3
0.8Nm
10
Dual VA Meter 30A – Current terminals
M4
1.2Nm
11
Dual VA Meter 30A – Voltage terminals
M4
1.2Nm
Operation:
• Ensure the door is closed.
• Rotate the Latch away from OFF push button
• Switch On the rocker switch.
• Check the status of amber LED. Wait till amber LED is continuously ON then only proceed.
• Depending upon Selector switch knob position for phase selection, Indication of incoming power
supply voltage can be seen on Dual VA meter.
• For starting the motor, press Green push button marked ‘I’ (Fig. 7)
• Line current of R phase is indicated by Dual VA meter.
• Indication of Motor ON can be seen on starter door through green LED.
• For stopping the motor press Red push button marked ‘O’ (Fig. 7)
Reset Operation
– If the overload relay trips, Reset manually.
(Allow a reset time of approx. 4 min.)
Note: For detail operation of WLCA , refer Installation, Maintenance & troubleshooting guide
Table: 20A Mounting torque values
Sr. No
Location
Size
Torque
1
Earthing screw (cover to body)
M5
1.2-1.6 Nm
2
Contactor 3TS30..33
M4
0.8-1.1Nm
3
LMR-A
M4
0.8-1.1Nm
4
Terminal block 30A
M4
0.8-1.1Nm
5
WLC
M4
0.8-1.1Nm
6
ON & OFF / Rest link
ST4.2x9.5
0.8-1.2Nm
7
Dual VA Meter
M4
0.2-0.3Nm
8
Selector Switch 3LD4
M4
0.8-1.1Nm
Содержание RAJA+ 3TE7131-1HC14-1A