background image

QVE1901U Flow Switch 

Technical Instructions 

 

Document Number 155-711 

 

September 20, 2012 

Siemens Industry, Inc. 

Page 7 

 

Specifications 

Functional data 

Field of use 

 

Suitable media 

water and water/glycol mixture 

Piping diameter 

3/4-inch to 8-inch (DN 20 to 200) 

Type of switch 

Reed contact 

 

Maximum contact voltage 

24 Vac/ 24 Vdc 

 

Maximum contact current 

1A 

 

Maximum switching capacity 

AC 26 VA/DC 20 W 

Switching point adjustment 

Manual, supplied with minimum  

   

switch-off 

value 

Tolerance of switching 
 

Point ranges in the table 

±

15% 

 Setting 

range 

See 

Switching Value 

Table 

Medium temp. 

–4°F to 230°F (–20°C to 110°C) 

 

(medium cannot freeze) 

 

Nominal pressure 

Maximum 365 psi 

Protective data 

Housing 

IP 65 per EN 60 529 

Environmental 
conditions 

General environmental conditions 
 

Operation and storage 

–4°F to 176°F (– 20°C to 80°C) 

 

Ambient humidity 

<95% rh 

Norms and standards 

 conformity to Low-voltage directive 

2006/95/ EEC 

Product standard 

EN 60204-1 

Materials/color 

Housing  

Polyamide, black (non-wetted component) 

Union nut 

Brass (non-wetted component) 

Body Brass 
Threaded adapter 1/2” NPT 

Brass 

Paddle system 

PPO (Noryl GFN3), black 

Axle Stainless 

Steel 

Magnet Hard 

ferrite 

Seal NBR 

Weight 

Excluding packaging 

10.93 ounces (0.31 kg) 

Maintenance and repair 

The flow switch is maintenance-free and cannot be repaired by the user. In the unlikely 
event of a defect, the device has to be returned to the manufacturer for repair. 

Decommissioning and 
disposal 

  

SEN0540R1

 

 

 

 

 

 

 

Never remove a flow switch or its upper parts from a system under pressure.

 

  Remove all the electrical connectors and disassemble the flow switch. 

  The flow switch consists of various materials (see 

Specifications

). Never dispose of the 

level switch in domestic waste. 

Содержание QVE1901U

Страница 1: ...ype NO NC Housing IP 65 excluding conduit adapter Maintenance free Application The QVE1901U Flow Switch is used in HVAC installations to monitor the flow of fluids in hydraulic systems especially in refrigeration heat pump and heating installations for example for use with condensers boilers heat exchangers and so on Product Number QVE1901U Warning Caution Notations WARNING Personal injury loss of...

Страница 2: ...ng on the contact type See Adjusting the Switching Unit Reed Contact 3 Paddle System 1 Shaft Flow Magnet 4 Magnet 2 SEN0528R1 N S N S Figure 1 Switching Value Table for Water at 68 F 20 C Make Contact NO Red Arrow Break Contact NC White Arrow 1 2 V SEN0529R1 1 2 V SEN0530R1 1 2 V SEN0530R1 1 2 V SEN0529R1 Line Size Inches mm Max Flow Rate gpm m 3 h Setpoints gpm m3 h Factory Setting Setpoints gpm ...

Страница 3: ...ter in the flow switch can result in frost damage Mechanical installation General installation instructions First clean the pipe system where the flow switch is installed and remove any magnetic particles such as welding residue The laminar path length in front of and behind the flow switch must be at least 10 times and 5 times the pipe diameter respectively The nominal installation position of th...

Страница 4: ...ons WARNING Danger of death due to electrical voltage Always disconnect power to the system before connecting wires of the main cable CAUTION Destruction or damage of reed contact Note the maximum contact loads stated on the type plate The maximum contact loads stated on the type plate switching voltage switching current and switching capacity refer to pure ohmic loads and may not be exceeded unde...

Страница 5: ...ly cable through the screwed conduit adapter g the pressure ring l and the rubber insert k into the cable socket d See Figure 8 Connect the wires as shown in the connection diagram below SEN0535R1 Reed Contact Reed Contact Not Occupied Not Occupied Reed Contact Not Occupied Reed Contact 1 2 3 1 2 3 Figure 9 Press the core j into the cable socket d until it locks into place See Figure 6 SEN0593R1 6...

Страница 6: ...ching head SEN0536R1 To Open Here Figure 10 Loosen the locking screw 0 1 2 5 mm hexagon socket screw and position the switching unit until the red or white arrow is visible at the entry of the switching contact guide to make contact or break contact respectively You can use the arrow length to make fine adjustments to the switching point Adjust to the arrowhead means Switching point is at a lower ...

Страница 7: ...conditions Operation and storage 4 F to 176 F 20 C to 80 C Ambient humidity 95 rh Norms and standards conformity to Low voltage directive 2006 95 EEC Product standard EN 60204 1 Materials color Housing Polyamide black non wetted component Union nut Brass non wetted component Body Brass Threaded adapter 1 2 NPT Brass Paddle system PPO Noryl GFN3 black Axle Stainless Steel Magnet Hard ferrite Seal N...

Страница 8: ... Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions Cutting the Paddle Line Size Inches mm L3 in mm 0 75 20 1 69 0 039 43 1 1 00 25 1 93 0 039 49 1 1 25 32 2 13 0 039 54 1 1 50 40 2 50 0 039 64 1 2 00 50 2 91 0 039 74 1 3 00 80 4 09 0 039 104 1 4 00 100 4 49 0 039 114 1 6 00 150 4 49 0 039 114 1 8 00 200 ...

Отзывы: