Technical Instructions  

QFM81 Series Duct Hygrostats 

Document Number 155-707 
April 21, 2010 

Page 4 

 

Siemens Industry, Inc. 

Specifications 

 

Setpoint range 

15 to 95% rh 

Control mode 

On / off 

Switching differential 

Approximately 4% rh (fixed) 

Type of switch 

Potential-free microswitch (SPDT) 

Contact rating 
 

Maximum  

5 (3) A, 24 Vac/Vdc 

 

Minimum   

100 mA, 24 Vac/Vdc 

Temperature influence 

Compensated 

Long-term stability 

Approximately 

1.5% rh/a 

Balancing 

At 55% rh, 73°F (23°C) 

Time constant (v = 0.2 m/s) 

Approximately 3 minutes 

Permissible air velocity 

10 m/s 

Permissible ambient temperature 
Operation 

32°F to 158°F (0°C to 70°C) 

Storage/transport 

–22°F to 158°F (

30 to 70°C) 

Degree of protection 

QFM81.2 

IP 30 to EN 60 529 

QFM81.21 

IP 55 to EN 60 529 

Safety class 

II to EN 60 730 

 conformity to low-voltage directive 

73 / 2 3 / EEC 

UL  

UL873 

cUL 

Canadian Standard C22.2 No. 24-93 

Connection terminals for  

20 AWG. minimum  

 

 

2 × 16 AWG

 

maximum 

Materials 

Sensing element 

Polymer 

Casing with stem 

PPS, Fortron 1140L6, fiberglass  

  

reinforced 

Cover 

PC Lexan 940 

Transparent cover 

PC Makrolon 2014R, transparent 

(only with QFM81.21) 

 

Weight 

Approximately 12 ounces (0.34 kg) 

Maintenance 

Maintenance-free, can be recalibrated 

 

Wiring Diagram 

 

SEN0510R1

1

2

3

 

1 – 2 Humidification 

1 – 3 Dehumidification 

Figure 3.  Wiring Connections. 

 

 

 

 

 

Содержание QFM81 Series

Страница 1: ...tpoint Range Wh Switching Differential Xd Degree of Protection Setpoint Adjustment QFM81 2 IP 30 Externally QFM81 21 15 to 95 r h Approx 4 rh IP 55 Internally NOTE Includes a mounting flange for duct or wall mounting and a sealing ring for duct mounting Mode of Operation The hygrostat acquires the relative humidity of the air with its humidity sensor which is a stabilized plastic strip The strip a...

Страница 2: ...ement stabilized plastic strip The strip is mechanically linked to the microswitch via a transfer lever Transfer lever microswitch setpoint setting element and connection terminals for connecting the humidification or dehumidification equipment are mounted on a printed circuit board inside the base The connection terminals are protected by a hinged cover to avoid direct access when the cover is re...

Страница 3: ...ity in the ductwork at 5 m s the holes in the stem must face the airflow at 5 m s they must be perpendicular to the direction of airflow see Figure 2 Minimum immersion length When mounting the hygrostat in air ducts the minimum immersion length of the stem 5 12 inches 130 mm must be observed The mounting flange supplied with the unit allows the immersion length to be adjusted between 5 12 inches 1...

Страница 4: ...Permissible ambient temperature Operation 32 F to 158 F 0 C to 70 C Storage transport 22 F to 158 F 30 to 70 C Degree of protection QFM81 2 IP 30 to EN 60 529 QFM81 21 IP 55 to EN 60 529 Safety class II to EN 60 730 conformity to low voltage directive 73 23 EEC UL UL873 cUL Canadian Standard C22 2 No 24 93 Connection terminals for 20 AWG minimum 2 16 AWG maximum Materials Sensing element Polymer C...

Страница 5: ...ndustry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions SEN0511R1 0 39 10 0 65 16 5 ø 1 18 ø 30 1 64 41 7 5 51 140 2 87 73 2 52 64 5 12 6 14 130 156 0 83 21 A B Pg 11 9 69 246 0 22 5 5 1 06 ...

Отзывы: