Siemens QFM81 Series Скачать руководство пользователя страница 1

 

 

 
 

 
 

QFM81 Series 

Technical Instructions

Document No. 155-707

April 21, 2010

 

Duct Hygrostats 
 

 

QFM81.21 

 

QFM81.2 

 

Siemens Industry, Inc. 

Description 

On / off hygrostat with microswitch, and temperature-compensated humidity sensor for 
temperature-independent humidity measurements. 

Features 

  Stabilized sensing strip (good linearity, very stable even at high humidity, insensitive 

to dust and contaminated air). 

  Can be mounted in ventilating ducts or rooms. 

Application 

For controlling humidification equipment and dehumidification equipment. 

Product Numbers 

 

Product 
Number 

Setpoint Range 

(W

h

Switching 

Differential 

(X

d

Degree of 

Protection 

Setpoint 

Adjustment 

QFM81.2 IP 

30 

Externally 

QFM81.21 

15 to 95% r.h. 

Approx. 4% rh 

IP 55 

Internally 

NOTE: 

Includes a mounting flange (for duct or wall mounting) and a sealing ring (for 
duct mounting).

 

Mode of Operation 

The hygrostat acquires the relative humidity of the air with its humidity sensor, which is 
a stabilized, plastic strip. The strip actuates a microswitch with a fixed switching 
differential X

d

 and a potential-free contact output (SPDT), depending on the relative 

humidity of the air. If the actual humidity deviates from the adjusted setpoint, the 
hygrostat switches the associated humidification or dehumidification equipment on or 
off as shown in the following function diagram (Figure 1). 

Содержание QFM81 Series

Страница 1: ...tpoint Range Wh Switching Differential Xd Degree of Protection Setpoint Adjustment QFM81 2 IP 30 Externally QFM81 21 15 to 95 r h Approx 4 rh IP 55 Internally NOTE Includes a mounting flange for duct or wall mounting and a sealing ring for duct mounting Mode of Operation The hygrostat acquires the relative humidity of the air with its humidity sensor which is a stabilized plastic strip The strip a...

Страница 2: ...ement stabilized plastic strip The strip is mechanically linked to the microswitch via a transfer lever Transfer lever microswitch setpoint setting element and connection terminals for connecting the humidification or dehumidification equipment are mounted on a printed circuit board inside the base The connection terminals are protected by a hinged cover to avoid direct access when the cover is re...

Страница 3: ...ity in the ductwork at 5 m s the holes in the stem must face the airflow at 5 m s they must be perpendicular to the direction of airflow see Figure 2 Minimum immersion length When mounting the hygrostat in air ducts the minimum immersion length of the stem 5 12 inches 130 mm must be observed The mounting flange supplied with the unit allows the immersion length to be adjusted between 5 12 inches 1...

Страница 4: ...Permissible ambient temperature Operation 32 F to 158 F 0 C to 70 C Storage transport 22 F to 158 F 30 to 70 C Degree of protection QFM81 2 IP 30 to EN 60 529 QFM81 21 IP 55 to EN 60 529 Safety class II to EN 60 730 conformity to low voltage directive 73 23 EEC UL UL873 cUL Canadian Standard C22 2 No 24 93 Connection terminals for 20 AWG minimum 2 16 AWG maximum Materials Sensing element Polymer C...

Страница 5: ...ndustry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions SEN0511R1 0 39 10 0 65 16 5 ø 1 18 ø 30 1 64 41 7 5 51 140 2 87 73 2 52 64 5 12 6 14 130 156 0 83 21 A B Pg 11 9 69 246 0 22 5 5 1 06 ...

Отзывы: