Siemens QFA2000 Скачать руководство пользователя страница 4

4/6 

Siemens Building Technologies 

Room sensors QFA20… 

CE1N1857en 

HVAC Products 

 

06.06.2005 

Commissioning notes 

Check wiring before switching on power. The temperature measuring range must be 
selected on the sensor, if required. 
Wiring and the output signals can be checked by making use of the test function (refer 
to "Mechanical design"). 

We recommend not to use voltmeters or ohmmeters directly at the sensing element. In 
the case of the simulated passive output signals, measurements with commercially 
available metres cannot be made (measuring current too small). 

Technical data 

Operating voltage 

AC 24 V 

±

20 % or DC 13.5...35 V 

Frequency 

50 / 60 Hz at AC 24 V 

Power consumption 

1 VA 

Perm. cable lengths 

refer to Data Sheet of the device  
handling the signal 

Range of use 

0…95 % r. h. (non-condensing) 

Measuring range 

0…100 % r. h. 

Measuring accuracy at 23 °C and AC 24 V 

0...95 % r.h. 
30...70 % r.h. 

 

±

5 % 

±

3 %, typically 

Temperature dependency 

0 . 1   %   r.  h. / ° C  

Time constant 

2 min 

Perm. air velocity 

20 m/s 

Output signal, linear (terminal U1) 

DC 0...10 V   0...100 % r. h.,  
max. 

±

1 mA 

Range of use 

15...+ 50 °C 

Measuring range 

0...50 °C / 

35...

+

35 °C 

Sensing element 

NTC 10 k

 

Measuring accuracy at  

15...35 °C 

35...+50 °C 

 

±

0.8 K 

±

1 K 

Time constant 

8 min (depending on air movement 
and thermal coupling to the wall) 

Output signal, linear (terminal U2) 

DC 0...10 V   0...50 °C / 

35...

+

35 °C 

max. 

±

1 mA 

Measuring range 

0...50 °C 

Sensing element simulated, corresponding to 

QFA2020 
QFA2040 (serie B or higher) 

 
LG-Ni 1000 
T1 (PTC) 

Measuring accuracy at  

15...35 °C 

35...+50 °C 

 

±

0.8 K 

±

1 K 

Time constant 

8 min (depending on air movement 
and thermal coupling to the wall) 

Perm. measuring current with 

QFA2020 
QFA2040 

 
1.18…3.29 mA 
0.53…1.46 mA 

Housing 

IP 30 to IEC 529 

Safety class 

III to EN 60 730 

Screw terminals for 

×

 2.5 mm

2

 oder 2 

×

 1.5 mm

2

 

.
.
.
.
.
.
.

 

Power supply 

Cable lengths for 
measuring signal  




.
.

Functional data of  
humidity sensor 



.
.
.

Functional data of  
temperature sensor with 
QFA2060 

Functional data of  
temperature sensor with  
QFA2020, QFA2040 


.
.

.



.
.

Degree of protection 

Electrical connections 

Содержание QFA2000

Страница 1: ...tive humidity and temperature in rooms The QFA20 is used as a control sensor and measuring sensor for building automation and control systems or indicating units Type summary Type reference Temperature measuring range Temperature signal output Humidity measuring range Humidity signal output Operating voltage QFA2000 None None 0 100 Active DC 0 10 V AC 24 V or DC 13 5 35 V QFA2020 0 50 C Passive LG...

Страница 2: ...T1 output signal The measuring current from systems devices für acquiring the electrical resistance of the passive sensor differs greatly and impacts self heating of the temperature sensing element at the end of the measuring probe To compensate the impact the passive output signal is simulated with an electronic circuit Characteristic LG Ni 1000 Characteristic T1 PTC 40 30 20 10 0 10 20 30 40 50 ...

Страница 3: ...re will be a voltage of 10 V at signal output U1 after 60 seconds and the temperature signal will remain active Engineering notes To power the sensor a transformer for safety extra low voltage SELV with separate windings for 100 duty is required When sizing and protecting the transformer the local safety regulations must be observed When sizing the transformer the power consumption of the room sen...

Страница 4: ...cally Temperature dependency 0 1 r h C Time constant 2 min Perm air velocity 20 m s Output signal linear terminal U1 DC 0 10 V 0 100 r h max 1 mA Range of use 15 50 C Measuring range 0 50 C 35 35 C Sensing element NTC 10 kΩ Measuring accuracy at 15 35 C 35 50 C 0 8 K 1 K Time constant 8 min depending on air movement and thermal coupling to the wall Output signal linear terminal U2 DC 0 10 V 0 50 C...

Страница 5: ...nt ASA PC NCS S 0502 G white Bottom section of housing ASA PC NCS 2801 Y43R grey Base PC NCS 2801 Y43R grey Sensor complete assembly silicon free Packaging corrugated cardboard Product safety Automatic electrical controls for household and similar use EN 60 730 1 Electromagnetic compatibility Immunity Emissions EN 61 000 6 1 EN 61 000 6 3 conformity to EMC directive 89 336 EEC conformity to Austra...

Страница 6: ...r h G G0 Operating voltage AC 24 V SELV or DC 13 5 35 V U1 Signal output DC 0 10 V for relative humidity 0 100 U2 Signal output DC 0 10 V for temperature range 0 50 C R2 factory setting or 35 35 C BS MS Signal output LG Ni 1000 oder T1 passive simulated for temperature range 0 50 C the wires must not be interchanged Dimensions 90 100 36 4 2 9 5 56 60 56 60 1857M01 Drilling plan Dimension in mm 200...

Отзывы: