Room sensors QFA20… 

CE1N1857en 

HVAC Products 

 

06.06.2005 

Ordering 

When ordering, please give name and type reference. 

Equipment combinations 

All systems or devices capable of acquiring and handling the sensor’s DC 0...10 V ,   
LG-Ni 1000 or T1 output signal. 
When using the passive sensors for averaging, we recommend to use the SEZ220 
signal converter (refer to Data Sheet N5146). 

Mode of operation 

The sensor acquires the relative humidity in the room via its capacitive humidity sens-
ing element whose electrical capacitance changes as a function of the relative humidity. 
The electronic measuring circuit converts the sensor’s signal to a continuous 
DC 0...10 V signal, which corresponds to 0...100 % relative humidity. 

The sensor acquires the temperature in the room via its sensing element whose electri-
cal resistance changes as a function of the temperature.  
Depending on the type of sensor, this change in resistance is converted either to an 
active DC 0…10 V output signal (   0… 50 °C or – 35…+ 35 °C) or is provided as a 
simulated passive LG-Ni 1000 or T1 output signal.  

The measuring current from systems / devices für acquiring the electrical resistance of 
the passive sensor differs greatly and impacts self-heating of the temperature sensing 
element at the end of the measuring probe. To compensate the impact, the passive 
output signal is simulated with an electronic circuit. 

Characteristic LG-Ni 1000 

Characteristic T1 (PTC) 

40

30

20

10

0

10

20

30

40 50

60 70

80

1400

1200

1000

800

600

[

]

[°C]

1811D0

1

50

ϑ

 

40

30

20

10

0

10

20

30

40 50

60 70

80

3000

2600

2200

1800

1400

[

]

[°C]

1864D0

1

ϑ

1600

2000

2400

2800

3200

 

Resistance value in Ohm 

ϑ

 

Temperature in degrees Celsius 

Mechanical design 

The units have been designed for wall mounting. They are suitable for use with most 
commercially available recessed conduit boxes. The cables can be introduced from the 
rear (concealed wiring) or from below or above (surface-run wires) through knock-out 
openings. 
The units consist of two major sections: Casing and baseplate. Both snap together but 
can be detached again.  
The measuring circuit, the sensing elements and the setting element are located on the 
printed circuit board inside the casing. 
The baseplate carries the connecting terminals. 

Relative humidity 

Temperature 

.
.
.
.
.
.
.
.

Simulated passive  
output signal 

Sensing elements,  
simulated 

Legend 

Содержание QFA2000

Страница 1: ...tive humidity and temperature in rooms The QFA20 is used as a control sensor and measuring sensor for building automation and control systems or indicating units Type summary Type reference Temperature measuring range Temperature signal output Humidity measuring range Humidity signal output Operating voltage QFA2000 None None 0 100 Active DC 0 10 V AC 24 V or DC 13 5 35 V QFA2020 0 50 C Passive LG...

Страница 2: ...T1 output signal The measuring current from systems devices für acquiring the electrical resistance of the passive sensor differs greatly and impacts self heating of the temperature sensing element at the end of the measuring probe To compensate the impact the passive output signal is simulated with an electronic circuit Characteristic LG Ni 1000 Characteristic T1 PTC 40 30 20 10 0 10 20 30 40 50 ...

Страница 3: ...re will be a voltage of 10 V at signal output U1 after 60 seconds and the temperature signal will remain active Engineering notes To power the sensor a transformer for safety extra low voltage SELV with separate windings for 100 duty is required When sizing and protecting the transformer the local safety regulations must be observed When sizing the transformer the power consumption of the room sen...

Страница 4: ...cally Temperature dependency 0 1 r h C Time constant 2 min Perm air velocity 20 m s Output signal linear terminal U1 DC 0 10 V 0 100 r h max 1 mA Range of use 15 50 C Measuring range 0 50 C 35 35 C Sensing element NTC 10 kΩ Measuring accuracy at 15 35 C 35 50 C 0 8 K 1 K Time constant 8 min depending on air movement and thermal coupling to the wall Output signal linear terminal U2 DC 0 10 V 0 50 C...

Страница 5: ...nt ASA PC NCS S 0502 G white Bottom section of housing ASA PC NCS 2801 Y43R grey Base PC NCS 2801 Y43R grey Sensor complete assembly silicon free Packaging corrugated cardboard Product safety Automatic electrical controls for household and similar use EN 60 730 1 Electromagnetic compatibility Immunity Emissions EN 61 000 6 1 EN 61 000 6 3 conformity to EMC directive 89 336 EEC conformity to Austra...

Страница 6: ...r h G G0 Operating voltage AC 24 V SELV or DC 13 5 35 V U1 Signal output DC 0 10 V for relative humidity 0 100 U2 Signal output DC 0 10 V for temperature range 0 50 C R2 factory setting or 35 35 C BS MS Signal output LG Ni 1000 oder T1 passive simulated for temperature range 0 50 C the wires must not be interchanged Dimensions 90 100 36 4 2 9 5 56 60 56 60 1857M01 Drilling plan Dimension in mm 200...

Отзывы: