1

857

 

 

 

 

 

 

 
Room Sensors 

QFA20…

 

for relative humidity and temperature 

 

 

 

Operating voltage AC 24 V  or DC 13.5…35 V 

 

Signal output DC 0...10 V  for relative humidity 

 

Signal output DC 0...10 V  or LG-Ni 1000 or T1 for temperature 

 

Accuracy of 

±

3 % r.h. within comfort range 

 

Range of use  

15…

+

50 °C / 0…95 % r. h. (non-condensing) 

Use 

In ventilating and air conditioning plants to acquire  

 relative humidity and 

 temperature 

in rooms. 

The QFA20… is used as a 

 control sensor and 

  measuring sensor for building automation and control systems or indicating units. 

Type summary 

Type  

reference 

Temperature  

measuring range 

Temperature  
signal output 

Humidity  

measuring range 

Humidity  

signal output 

Operating voltage 

QFA2000 

None 

None 

0...100 % 

Active, DC 0...10 V 

AC 24 V or DC 13.5…35 V 

QFA2020 

0...50 °C 

Passive, LG-Ni 1000 

0...100 % 

Active, DC 0...10 V 

AC 24 V or DC 13.5…35 V 

QFA2040 

0...50 °C 

Passive, T1 

0...100 % 

Active, DC 0...10 V 

AC 24 V or DC 13.5…35 V 

QFA2060 

0...50 °C / 

35...

+

3 5  °C 

Active, DC 0...10 V 

0...100 % 

Active, DC 0...10 V 

AC 24 V or DC 13.5…35 V 

.
.
.
.

185

7P0

1

 

Содержание QFA2000

Страница 1: ...tive humidity and temperature in rooms The QFA20 is used as a control sensor and measuring sensor for building automation and control systems or indicating units Type summary Type reference Temperature measuring range Temperature signal output Humidity measuring range Humidity signal output Operating voltage QFA2000 None None 0 100 Active DC 0 10 V AC 24 V or DC 13 5 35 V QFA2020 0 50 C Passive LG...

Страница 2: ...T1 output signal The measuring current from systems devices für acquiring the electrical resistance of the passive sensor differs greatly and impacts self heating of the temperature sensing element at the end of the measuring probe To compensate the impact the passive output signal is simulated with an electronic circuit Characteristic LG Ni 1000 Characteristic T1 PTC 40 30 20 10 0 10 20 30 40 50 ...

Страница 3: ...re will be a voltage of 10 V at signal output U1 after 60 seconds and the temperature signal will remain active Engineering notes To power the sensor a transformer for safety extra low voltage SELV with separate windings for 100 duty is required When sizing and protecting the transformer the local safety regulations must be observed When sizing the transformer the power consumption of the room sen...

Страница 4: ...cally Temperature dependency 0 1 r h C Time constant 2 min Perm air velocity 20 m s Output signal linear terminal U1 DC 0 10 V 0 100 r h max 1 mA Range of use 15 50 C Measuring range 0 50 C 35 35 C Sensing element NTC 10 kΩ Measuring accuracy at 15 35 C 35 50 C 0 8 K 1 K Time constant 8 min depending on air movement and thermal coupling to the wall Output signal linear terminal U2 DC 0 10 V 0 50 C...

Страница 5: ...nt ASA PC NCS S 0502 G white Bottom section of housing ASA PC NCS 2801 Y43R grey Base PC NCS 2801 Y43R grey Sensor complete assembly silicon free Packaging corrugated cardboard Product safety Automatic electrical controls for household and similar use EN 60 730 1 Electromagnetic compatibility Immunity Emissions EN 61 000 6 1 EN 61 000 6 3 conformity to EMC directive 89 336 EEC conformity to Austra...

Страница 6: ...r h G G0 Operating voltage AC 24 V SELV or DC 13 5 35 V U1 Signal output DC 0 10 V for relative humidity 0 100 U2 Signal output DC 0 10 V for temperature range 0 50 C R2 factory setting or 35 35 C BS MS Signal output LG Ni 1000 oder T1 passive simulated for temperature range 0 50 C the wires must not be interchanged Dimensions 90 100 36 4 2 9 5 56 60 56 60 1857M01 Drilling plan Dimension in mm 200...

Отзывы: