6 / 36
Siemens
Room Unit for Boiler Control
CE1U2283en
Building Technologies
Mounting and Installation
2015-09-16
1.2 Product
liability
·
The products may only be used in building services plant and applications as
described above
·
When using the products, all requirements specified under "Technical data"
must be observed
·
The local regulations for electrical installation must be complied with
1.3 Disposal
The device is classified as waste electronic equipment in terms of the European
Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted muni-
cipal waste.
The relevant national legal rules must be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.
2
Mounting
and
Installation
2.1 Engineering
·
In the main living room or reference room
·
The place of installation should be chosen so that the sensor can capture the
room temperature as accurately as possible, without being affected by direct
solar radiation or other heating or cooling sources.
·
Mounting height is about 1.5 meters above the floor
·
The unit can be fitted to most commercially available recessed conduit boxes or
directly on the wall.
Mounting location