Page 72
Pointek CLS500 – INSTRUCTION MANUA
7ML19985GG03
mmmmm
Appendix A
Menu selections 03, 04, 05, and 06 set the criteria for delay and threshold that have to be
met for a change in output signal.
Set the rotary switch to 7. To change the mode to 2-state High, press the RED (+) button
for more than one second: the LCD displays C: Hi. When the button is released, the loop-
current will switch to 20 mA if the probe is covered, or 4 mA if it is uncovered.
To change the mode to 2-state Low, press the BLUE (–) button for more than one second:
the LCD displays C: Lo. When the button is released, the loop-current will switch to 4 mA,
and if the probe is uncovered, or 20 mA if the probe is covered.
While the device is in either FailSafe High or FailSafe Low mode, it reads the loop current
as 4 or 20 mA (no faults) or 3.6 or 22 mA (fault situation).
(Analog Mode is only available when Free Programming Mode is selected at menu 1E: in
that case it may be restored at any time by pressing both buttons simultaneously for more
than one second. The LCD displays C: An while the two buttons are pressed, and displays
the current reading when the buttons are released.The loop-current will be between 3.8
and 20.5 mA, and will saturate to one of these values if the level goes beyond the Upper
or Lower range settings.)
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Description Action
Values
07
03, 04, 05,
06, 08
7
Off
Analog
a
a.
Unavailable when FSH or FSL mode is selected at menu 1E: available only if
FPM (Free Programming Mode) is selected.
Signal
proportional to
% of range
b
b.
This option is available, but not useful for Pointek CLS500.
Press both
buttons
simultaneously
Display
shows
C: An
2-state
* 2-state High
Press RED (+)
Display
shows
C: Hi
c
c.
While button is pressed, display reads C: Hi. When button is released, display
shows 20.00 if the probe is covered, or 4.00 if it is uncovered.
2-state Low
Press BLUE (–)
Display
shows
C: Lo
d
d.
While button is pressed, display reads C: Lo. When button is released, display
shows 4.00 if the probe is covered, or 20.00 if it is uncovered.