Siemens PMI-2 Скачать руководство пользователя страница 5

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-050636-1

5

TO UPGRADE FROM

Follow the procedure below to upgrade an XLS panel from a PMI to a PMI-2.

PMI TO  PMI-2

1.

Please ensure you are using Zeus 8.1.0 or greater.

2.

Create a new project in Zeus (

File>New

) to avoid overwriting a current

project.  The new project’s filename is not important.

3.

Download the current configuration from the PMI.
a) Connect the Laptop via the Upload cable and select

Build>Transfer>Configuration From Panel.

b) An .hrc configuration file from the PMI control panel downloads to the

Zeus host PC. Initially, the Zeus Transfer dialog will open, with settings for
serial port and transfer protocol. Once these are set, the Transfer Con-
figuration dialog will display information the PMI’s current configuration,
software and firmware versions. You can select the panel from which to
download (if there are multiple compiled configurations in the host PC),
and also choose to download the PMI’s current history file into the
project directory. Once you have begun the transfer, the Transfer
Progress dialog displays transfer progress and status messages, and
allows you to cancel the transfer.

4.

Once the panel configuration is downloaded, close the new project, use

Tools > Decompile

 to open the downloaded .hrc configuration file as a

project in Zeus.

5.

In the Zeus tool replace the PMI with the new PMI-2.

Please make sure you are converting the correct PMI with a PMI-2 by matching the

address of the switches on the back of the PMI.

a) In the configuration which you have just removed from the original PMI,

click on the PMI module in the physical tree. Select the Edit menu and
click on “

Find/Replace Tree  Node

”. A dialog box will open and allow you

to replace the PMI with the PMI-2.

b) Once this is completed, save and then compile the configuration.

Remove ELECTRICAL POWER prior to removing the original PMI and installing the
new PMI-2 in the enclosure.

c) Physically remove the original PMI and install the new PMI-2 on the inner

door of the enclosure. (For more detail see the INSTALLATION section
and Figure 4 of this document.)

d) Re-attach the 60-pin cable to the connector at the top of the PMI-2 (see

Figures 5 and 6) as well as any other original connections to the PMI.

e) Apply power and allow the unit to initialize.

6.

Transfer the configuration to the Panel.
a) Connect the USB programming cable to the PMI-2 USB type B connector

labeled “UPLOAD” at the bottom of the unit. (Refer to Figure 2.)

b)  In the Zeus configuration, select the module in the Physical Tree. Then

select 

Build>Transfer>Configuration to Panel

. An .hrc configuration file

uploads from the Zeus host PC to the PMI-2 control panel, overwriting
the existing configuration in the panel.
i) Initially, the Zeus Transfer dialog will open, with settings for serial port

and transfer protocol. Once these settings are made, the Transfer

Содержание PMI-2

Страница 1: ... PMI 2 contains the site specific program as developed in Zeus All system logic and supervision is provided by the controller in the PMI 2 The PMI 2 contains a full VGA LCD Touch Screen and LEDs for display ing system status An audible sounds when there are unacknowledged events on the PMI 2 The display is surrounded by keys that are used to control the displayed information and to navigate throug...

Страница 2: ...a b d n a e s a b a t a d 2 D S I M P G w o l l a o t d e s u t r o p d r a c D S y t i l i b a p a c S U T A T S l a m r o n e t a c i d n i o t t h g i l s t n e m g e s g n i k l a W n a f i d e y a l p s i d s i e d o c r o r r E n o i t a r e p o d e t c e t e d s i D I r o r r e l a n r e t n i 5 C C O T 5 C C o t e l b a c n o b b i r n i p 0 6 s t c e n n o C M V L O T s u b o i d u a g o ...

Страница 3: ... o i t p O 4 S n o g n i t t e s o N t i g i d o w t e h t o t s s e r d d a e d o n T E N X e h t t e S s u e Z n i t i r o f d e n g i s s a s s e r d d a N O o t 4 n o i t i s o p h c t i w s s n o i t p O 7 1 S t e S t i g i d e e r h t e h t o t s s e r d d a e d o n T E N X e h t t e S s u e Z n i t i r o f d e n g i s s a s s e r d d a s u e Z n i g n i t t e S m o r f s s e r d d a e d o n...

Страница 4: ...he local audible Once all events are acknowl edged a reset button becomes available in the lower right side of the display If notification appliances were active two additional buttons appear at the bottom of the screen These allow the operator to silence or unsilence the notification appli ances When the notification appliances are silenced the Audibles Silenced LED lights The system can only be ...

Страница 5: ...he Zeus tool replace the PMI with the new PMI 2 Please make sure you are converting the correct PMI with a PMI 2 by matching the address of the switches on the back of the PMI a In the configuration which you have just removed from the original PMI click on the PMI module in the physical tree Select the Edit menu and click on Find ReplaceTree Node A dialog box will open and allow you to replace th...

Страница 6: ... into the project directory ii Once you have begun the transfer theTransfer Progress dialog displays transfer progress and status messages and allows you to cancel the transfer When you click OK at the transfer complete message the control panel will reset itself with the new configuration ELECTRICAL RATINGS r e w o P t u p n I r e w o P t u p t u O t n e r r u C e n a l P k c a B V 4 2 A m 5 9 1 ...

Отзывы: