Input 1
5
4
Input 2
PAD-3
AUX
18
NAC
12
Trouble
Relay
NAC
10 11
15
14
13
NAC
NAC
17
16
+
-
19
20 21
- +
- +
- +
-
P/N 140-820405
24K EOL
Supervised
Notification
Circuits
Class B
24K, 1W EOL
P/N 140-033771
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
+
-
+
NC
NC
NC
NC
-
+
-
+
-
+
-
+
-
17
18
19
20
21
22
23
24
ZONE 2
ZONE 4
STYLE Y
CLASS B
STYLE Y
CLASS B
ZONE 1
INPUT
ZONE 2
INPUT
ZONE 3
INPUT
ZONE 4
INPUT
ONE SLOT OF CC-5
24K,
1W
5%
24K,
1W
5%
FOR CANADIAN APPLICATIONS,
USE EOL MODEL REL-EOL.
OMIT THE DIODE.
*
*
*
*
+
POLARIZED
NOTIFICATION
APPLIANCES
NC
NC
AC Fail
Figure 3-10. Connection to ZIC-4A (FireFinder-XLS)
NOTES:
1.
All wiring must be in accordance
with Article 760 of NEC or local
building codes. Wiring for each
zone can either be Class A or
Class B.
2.
All output circuits are power limited
to NFPA 70 per NEC 760.
3. Electrical
Ratings:
Output
Zone
Supervisory:
4mA max @ 24VDC
Output
Zone
Alarm:
4A max @ 24VDC
4.
EOL resistor, 24K ohms, 1 watt,
5%, P/N 140-033771.
5.
Polarity shown in active state.
6.
Maximum line resistance is
dependent upon the maximum
current draw of connected
notification appliances when
activated. The field wiring
resistance cannot exceed the
maximum line resistance specified
for any given NAC current draw
(See Table below).
7.
ZIC output must be configured as
NAC, NAC-Coded or Sync Strobe
only. All other usages are not
applicable.
8.
Refer to the Zeus Quick Start
Manual (P/N 315-033875) and
ZIC-4A Installation Instructions
(P/N 315-033050) for additional
information.
Current
Draw
Max Line
Resistance
4.0A
0.8 ohms
3.5A
1.0 ohms
3.0A
1.2 ohms
2.5A
1.5 ohms
2.0A
2.0 ohms
1.5A
2.7 ohms
1.0A
4.2 ohms
0.5A
8.7 ohms