Installation Instructions 

Document No. 553-140  

November 4, 2019 

 

TX-I/O P1 Bus Interface Module 

     

 

Item Number:  553-140, Rev. GA

 

Page 1 of 4 

Product Description 

The P1 Bus Interface Module (P1 BIM) enables 
communication between a P1 Field Level Network 
(FLN) and TX-I/O modules. It also provides 14.4 W 
(0.6A at 24 Vdc) to power the TX-I/O modules and 
external devices. External devices draw power from 
the 24 Vdc and ground terminals on the TX-I/O 
modules. 

 

Figure 1.  P1 Bus Interface Module Example (TXB1.P1-4). 

Product Numbers 

TXB1.P1 

TX-I/O Bus Interface Module, P1 
(10 modules, if needed may share 
power with TXS1.12F4 TX-I/O 
Power Supply) 

TXB1.P1-4 

TX-I/O Bus Interface Module, P1 
(4 modules) 

Warning/Caution Notation 

WARNING: 

 

 

Personal injury or property 
damage may occur if you do not 
follow a procedure as specified. 

CAUTION: 

 

 

Equipment damage or loss of 
data may occur if you do not 
follow a procedure as specified. 

 

Required Tools and Materials 

 

Wire stripper/side cutter  

 

Small flat blade screwdriver 

 

Digital multimeter (DMM) 

Expected Installation Time 

7 minutes 

Prerequisites 

 

CAUTION: 

 

No power wiring is connected to the field 
panel controller or other TX-I/O 
components at this time. 

 

CAUTION: 

 

The TX-I/O island bus must be mounted 
on a DIN rail (1.38" × 0.3" × 0.04" 
[35 mm × 7.5 mm × 1 mm]). 

 

For energy management installations, NEMA 
Type 1 or better enclosure with DIN rails and 
source of 24 Vac. 

 

For smoke control installations, PX Series 
enclosures and service boxes. See the 

PX 

Series Service Box Installation Instructions

 

(553-131). 

 

If mounting in an enclosure: 

 

Enclosure is installed. 

 

The power source is installed, as 
applicable. 

 

The power is OFF. 

 

All necessary wiring is pulled and terminated 
per the layout drawing. 

 

Power and communication wiring is terminated 
to the removable plugs supplied with the 
devices.  

Содержание P1 BIM

Страница 1: ... as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Required Tools and Materials Wire stripper side cutter Small flat blade screwdriver Digital multimeter DMM Expected Installation Time 7 minutes Prerequisites CAUTION No power wiring is connected to the field panel controller or other TX I O components at this time CAUTION The TX I O islan...

Страница 2: ...us System Neutral must be connected to building approved earth ground at a single point only at the 24 Vac transformer Installation CAUTION Turn OFF AC power at the ON OFF switch in the Service Box or transformer enclosure CAUTION UL Listings require that NEC Class I and Class II wiring be kept separate from each other Use separate conduit and cable tie bars to separate Class I Digital Output DO w...

Страница 3: ...X I O island bus connector 5 Push in each mounting tab until it clips onto the DIN rail Connecting Devices to the TX I O Island Bus Completing the Installation CAUTION For RS 485 ALN or FLN terminate only one end of the shield wire on the enclosure earth ground For a 3 wire system terminal is connected to reference wire Protective ground terminal may be connected to earth ground For a 2 wire syste...

Страница 4: ...ed in the USA Page 4 of 4 Configuring the 4 Module P1 BIM 1 Power up the P1 BIM 2 Plug in the USB on both ends the device side to the P1 BIM the host side to the computer The device will be automatically recognized and installed 3 Open Windows Explorer 4 Find the USB device drive will say SIEMENS P1BIM Configuration Tool in the drives list 5 Open the drive 6 Double click P1BIMCFG exe to launch the...

Отзывы: